Plan Review Notes
Plan Review Notes For Permit 20060201
Permit Number 20060201
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2020-07-01 15:28:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF THE CHANGES/REVISIONS ON
 THE SUBMITTED PLANS NOR ANY NARRATIVE EXPLAINING THE
 CHANGES.
  
 PER NFPA 1
  
 1.14 PLAN REVIEW.
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE PROVIDE CLOUDED CHANGES ON THE PLAN SHEETS OR A
 DETAILED NARRATIVE FOR EACH CHANGE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 THE FOLLOWING COMMENTS WERE FROM THE ORIGINAL REVIEW
 THAT HAVE NOT BEEN ADDRESSED WITH ANY KIND OF CLARITY.
  
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IT APPEARS THAT THERE IS NO RE-ENTRY WITHIN THE
 STAIRWELLS.
  
 PER NFPA 101 CH 28 AND CH 7,
  
 28.2.2.2 DOORS.
 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 28.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH
 28.2.2.2.2.1, 28.2.2.2.2.2, 28.2.2.2.2.3, OR
 28.2.2.2.2.4.
 28.2.2.2.2.1 NO DOOR IN ANY MEANS OF EGRESS SHALL BE
 LOCKED
 AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED.
 28.2.2.2.2.2 DELAYED-EGRESS LOCKS COMPLYING WITH
 7.2.1.6.1 SHALL
 BE PERMITTED.
 28.2.2.2.2.3 ACCESS-CONTROLLED EGRESS DOORS COMPLYING
 WITH
 7.2.1.6.2 SHALL BE PERMITTED.
  
 7.2.1.5.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE
 SERVING MORE
 THAN FOUR STORIES, UNLESS PERMITTED BY 7.2.1.5.8.2,
 SHALL MEET ONE
 OF THE FOLLOWING CONDITIONS:
 (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR
 OF THE
 BUILDING SHALL BE PROVIDED.
 (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE
 INITIATION OF
 THE BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO
 UNLOCK ALL
 STAIR ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY.
 (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE
 WITH
 7.2.1.5.8.1.
 7.2.1.5.8.1 DOOR ASSEMBLIES ON STAIR ENCLOSURES SHALL
 BE PERMITTED
 TO BE EQUIPPED WITH HARDWARE THAT PREVENTS RE-ENTRY
 INTO THE
 INTERIOR OF THE BUILDING, PROVIDED THAT ALL OF THE
 FOLLOWING CRITERIA
 ARE MET:
 (1) THERE SHALL BE NOT LESS THAN TWO LEVELS WHERE IT IS
 POSSIBLE TO
 LEAVE THE STAIR ENCLOSURE TO ACCESS ANOTHER EXIT.
 (2) THERE SHALL BE NOT MORE THAN FOUR STORIES
 INTERVENING
 BETWEEN STORIES WHERE IT IS POSSIBLE TO LEAVE THE STAIR
 ENCLOSURE TO ACCESS ANOTHER EXIT.
 (3) RE-ENTRY SHALL BE POSSIBLE ON THE TOP STORY OR
 NEXT-TO-TOP
 STORY SERVED BY THE STAIR ENCLOSURE, AND SUCH STORY
 SHALL ALLOW
 ACCESS TO ANOTHER EXIT.
 (4) DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE
 IDENTIFIED AS SUCH
 ON THE STAIR SIDE OF THE DOOR LEAF.
 (5) DOOR ASSEMBLIES NOT ALLOWING RE-ENTRY SHALL BE
 PROVIDED WITH
 A SIGN ON THE STAIR SIDE INDICATING THE LOCATION OF THE
 NEAREST
 DOOR OPENING, IN EACH DIRECTION OF TRAVEL, THAT ALLOWS
 RE-ENTRY
 OR EXIT.
  
 PLEASE REVIEW, CORRECT AND PROVIDE DETAILS.
  
  
  
 2) STAIRS S 101 - THER APPEAARS TO BE ACCESS CONRTOL
 LIMITING THE EXIT FROM WITHIN THE STAIRWELL WITHOUT A
 CARDER READER.
  
 THOUGH THIS STAIR MAY NOT BE A REQUIRED EGRESS IF A
 PERSON IS ALLOWED TO ENTER IT, FROM ANY FLOOR, HOW
 WOULD THEY BE ABLE TO EXIT IT AT ANY FLOOR?
  
 28.2.2.2.2.3 ACCESS-CONTROLLED EGRESS DOORS COMPLYING
 WITH
 7.2.1.6.2 SHALL BE PERMITTED.
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR ASSEMBLIES IN
 THE
 MEANS OF EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH
 ELECTRICAL
 LOCK HARDWARE THAT PREVENTS EGRESS, PROVIDED THAT ALL
 OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO
 UNLOCK THE DOOR LEAF IN THE DIRECTION OF EGRESS UPON
 DETECTION
 OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS
 UPON LOSS OF POWER TO THE SENSOR OR TO THE PART OF THE
 ACCESS
 CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF
 EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH ALL
 OF
 THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS
 SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM) VERTICALLY
 ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM) OF THE
 SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE
 AND CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS:
 PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN
 DIRECT INTERRUPTION OF POWER TO THE LOCK ? INDEPENDENT
 OF THE LOCKING SYSTEM ELECTRONICS ? AND THE LOCK SHALL
 REMAIN UNLOCKED FOR NOT LESS THAN 30 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF
 PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES IN
 THE
 DIRECTION OF EGRESS, AND THE DOOR LEAVES SHALL REMAIN
 UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS
 BEEN
 MANUALLY RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE
 BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM SPECIFIED IN
 7.2.1.6.2(4) SHALL NOT BE REQUIRED TO UNLOCK THE DOOR
 LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE
 DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE
 DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR
 LEAVES
 SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING
 SYSTEM HAS BEEN MANUALLY RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN
 EXISTING ACCESS-CONTROLLED EGRESS DOORS, SHALL BE
 PROVIDED
 WITH EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 7.9.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]