2020-07-01 15:28:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE ARE NO INDICATIONS OF THE CHANGES/REVISIONS ON |
| THE SUBMITTED PLANS NOR ANY NARRATIVE EXPLAINING THE |
| CHANGES. |
| |
| PER NFPA 1 |
| |
| 1.14 PLAN REVIEW. |
| 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION |
| DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND |
| SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE |
| CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD |
| CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. |
| |
| PLEASE PROVIDE CLOUDED CHANGES ON THE PLAN SHEETS OR A |
| DETAILED NARRATIVE FOR EACH CHANGE. |
| |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| |
| THE FOLLOWING COMMENTS WERE FROM THE ORIGINAL REVIEW |
| THAT HAVE NOT BEEN ADDRESSED WITH ANY KIND OF CLARITY. |
| |
| |
| |
| THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) IT APPEARS THAT THERE IS NO RE-ENTRY WITHIN THE |
| STAIRWELLS. |
| |
| PER NFPA 101 CH 28 AND CH 7, |
| |
| 28.2.2.2 DOORS. |
| 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| 28.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH |
| 28.2.2.2.2.1, 28.2.2.2.2.2, 28.2.2.2.2.3, OR |
| 28.2.2.2.2.4. |
| 28.2.2.2.2.1 NO DOOR IN ANY MEANS OF EGRESS SHALL BE |
| LOCKED |
| AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED. |
| 28.2.2.2.2.2 DELAYED-EGRESS LOCKS COMPLYING WITH |
| 7.2.1.6.1 SHALL |
| BE PERMITTED. |
| 28.2.2.2.2.3 ACCESS-CONTROLLED EGRESS DOORS COMPLYING |
| WITH |
| 7.2.1.6.2 SHALL BE PERMITTED. |
| |
| 7.2.1.5.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE |
| SERVING MORE |
| THAN FOUR STORIES, UNLESS PERMITTED BY 7.2.1.5.8.2, |
| SHALL MEET ONE |
| OF THE FOLLOWING CONDITIONS: |
| (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR |
| OF THE |
| BUILDING SHALL BE PROVIDED. |
| (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE |
| INITIATION OF |
| THE BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO |
| UNLOCK ALL |
| STAIR ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY. |
| (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE |
| WITH |
| 7.2.1.5.8.1. |
| 7.2.1.5.8.1 DOOR ASSEMBLIES ON STAIR ENCLOSURES SHALL |
| BE PERMITTED |
| TO BE EQUIPPED WITH HARDWARE THAT PREVENTS RE-ENTRY |
| INTO THE |
| INTERIOR OF THE BUILDING, PROVIDED THAT ALL OF THE |
| FOLLOWING CRITERIA |
| ARE MET: |
| (1) THERE SHALL BE NOT LESS THAN TWO LEVELS WHERE IT IS |
| POSSIBLE TO |
| LEAVE THE STAIR ENCLOSURE TO ACCESS ANOTHER EXIT. |
| (2) THERE SHALL BE NOT MORE THAN FOUR STORIES |
| INTERVENING |
| BETWEEN STORIES WHERE IT IS POSSIBLE TO LEAVE THE STAIR |
| ENCLOSURE TO ACCESS ANOTHER EXIT. |
| (3) RE-ENTRY SHALL BE POSSIBLE ON THE TOP STORY OR |
| NEXT-TO-TOP |
| STORY SERVED BY THE STAIR ENCLOSURE, AND SUCH STORY |
| SHALL ALLOW |
| ACCESS TO ANOTHER EXIT. |
| (4) DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE |
| IDENTIFIED AS SUCH |
| ON THE STAIR SIDE OF THE DOOR LEAF. |
| (5) DOOR ASSEMBLIES NOT ALLOWING RE-ENTRY SHALL BE |
| PROVIDED WITH |
| A SIGN ON THE STAIR SIDE INDICATING THE LOCATION OF THE |
| NEAREST |
| DOOR OPENING, IN EACH DIRECTION OF TRAVEL, THAT ALLOWS |
| RE-ENTRY |
| OR EXIT. |
| |
| PLEASE REVIEW, CORRECT AND PROVIDE DETAILS. |
| |
| |
| |
| 2) STAIRS S 101 - THER APPEAARS TO BE ACCESS CONRTOL |
| LIMITING THE EXIT FROM WITHIN THE STAIRWELL WITHOUT A |
| CARDER READER. |
| |
| THOUGH THIS STAIR MAY NOT BE A REQUIRED EGRESS IF A |
| PERSON IS ALLOWED TO ENTER IT, FROM ANY FLOOR, HOW |
| WOULD THEY BE ABLE TO EXIT IT AT ANY FLOOR? |
| |
| 28.2.2.2.2.3 ACCESS-CONTROLLED EGRESS DOORS COMPLYING |
| WITH |
| 7.2.1.6.2 SHALL BE PERMITTED. |
| |
| 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES. |
| WHERE |
| PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR ASSEMBLIES IN |
| THE |
| MEANS OF EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH |
| ELECTRICAL |
| LOCK HARDWARE THAT PREVENTS EGRESS, PROVIDED THAT ALL |
| OF THE |
| FOLLOWING CRITERIA ARE MET: |
| (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| ARRANGED TO |
| UNLOCK THE DOOR LEAF IN THE DIRECTION OF EGRESS UPON |
| DETECTION |
| OF AN APPROACHING OCCUPANT. |
| (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE |
| DIRECTION OF EGRESS |
| UPON LOSS OF POWER TO THE SENSOR OR TO THE PART OF THE |
| ACCESS |
| CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES. |
| (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE |
| DIRECTION OF |
| EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH ALL |
| OF |
| THE FOLLOWING CRITERIA: |
| (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE |
| EGRESS |
| SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM) VERTICALLY |
| ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM) OF THE |
| SECURED DOOR OPENINGS. |
| (B) THE MANUAL RELEASE DEVICE SHALL BE READILY |
| ACCESSIBLE |
| AND CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS: |
| PUSH TO EXIT. |
| (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| RESULT IN |
| DIRECT INTERRUPTION OF POWER TO THE LOCK ? INDEPENDENT |
| OF THE LOCKING SYSTEM ELECTRONICS ? AND THE LOCK SHALL |
| REMAIN UNLOCKED FOR NOT LESS THAN 30 SECONDS. |
| (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE |
| SIGNALING SYSTEM, IF |
| PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES IN |
| THE |
| DIRECTION OF EGRESS, AND THE DOOR LEAVES SHALL REMAIN |
| UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS |
| BEEN |
| MANUALLY RESET. |
| (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT |
| ACTIVATE THE |
| BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM SPECIFIED IN |
| 7.2.1.6.2(4) SHALL NOT BE REQUIRED TO UNLOCK THE DOOR |
| LEAVES. |
| (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR |
| FIRE |
| DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY |
| UNLOCK THE |
| DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR |
| LEAVES |
| SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE |
| SIGNALING |
| SYSTEM HAS BEEN MANUALLY RESET. |
| (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS, |
| OTHER THAN |
| EXISTING ACCESS-CONTROLLED EGRESS DOORS, SHALL BE |
| PROVIDED |
| WITH EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 7.9. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |