Plan Review Notes
Plan Review Notes For Permit 20060201
Permit Number 20060201
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2020-06-24 12:38:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF THE CHANGES/REVISIONS ON
 THE SUBMITTED PLANS NOR ANY NARRATIVE EXPLAINING THE
 CHANGES.
  
 PER NFPA 1
  
 1.14 PLAN REVIEW.
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE PROVIDE CLOUDED CHANGES ON THE PLAN SHEETS OR A
 DETAILED NARRATIVE FOR EACH CHANGE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  