2020-07-27 16:17:43 | 1ST REVIEW FBC-2017 RES. |
| PERMIT- 20060195 |
| 7/27/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET S1 PLUMBING RISER: NO VENT IS SHOWN FOR THE |
| WASHING MACHINE- SECTION P3101.2.1 FBC RES. AN |
| INDIVIDUAL 2" VENT WILL BE REQUIRED BECAUSE ONLY THE |
| FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO |
| THE WET-VENTED HORIZONTAL BRANCH DRAIN- SECTION P3108.1 |
| 2) PROVIDE A WATER DISTRIBUTION RISER DRAWING SHOWING |
| THE PIPING RUNS, PIPE SIZES, AND SHUT OFF VALVE |
| LOCATIONS- SECTION 107.3.5.3 WPB. PLEASE INCLUDE THE |
| SUPPLY LINES TO THE DISHWASHER AND REFRIGERATOR ICE |
| MAKER SHOWING THE REQUIRED BACKFLOW PREVENTERS AND |
| WATER HAMMER ARRESTORS- SECTIONS P2717.1, P2902.1 |
| P2903.5 FBC RES. |
| |
| 3) SHOW THE LOCATIONS OF THE WASHING MACHINE SUPPLY |
| VALVES TO VERIFY THEY WILL BE ACCESSIBLE- SECTION |
| P2903.9.3 FBC RES. |
| |
| 4) PROVIDE A SHOWER PAN DETAIL- SECTIONS P2709.1 & |
| P2709.2 FBC RES. |
| |
| 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| HEATER- SECTION P2801.3 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |