2020-07-21 08:23:12 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20060195 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC E FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE ENERGY CALCULATIONS. FBC EC |
| 101.5.1.1.2 |
| |
| 2) PLEASE PROVIDE MANUAL J CALCULATIONS FOR THE |
| MECHANICAL SYSTEM SIZING. FBC EC R403.7 |
| |
| 3) PLEASE PROVIDE SPECIFICATIONS FOR THE AHU AND |
| CONDENSING UNITS. FBC FS 107.2.1 |
| |
| 4) PLEASE SHOW CONDENSATION PIPING AND TERMINATION |
| LOCATION. FBC RES M1411.3 |
| |
| 5) PLEASE PROVIDE MECHANICAL SHEETS SHOWING THE |
| LOCATION OF THE AHU, CONDENSING UNIT, THERMOSTAT |
| LOCATION DUCTS AND DUCT SIZES. THE RETURN AIR PATH BACK |
| TO THE UNIT. PLEASE ALSO SHOW BATH EXHAUST FAN LOCATION |
| AND VENT TERMINATION LOCATION. PLEASE ALSO SHOW THE |
| DRYER DUCT LENGTH AND TERMINATION LOCATION. PLEASE ALSO |
| PROVIDE A DETAIL FOR SECURING THE CONDENSING UNIT TO |
| PAD. FBC FS 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |