2020-09-22 15:42:31 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT-20060169 |
| |
| CODES IN EFFECT: |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE APPLICATION FOR PERMIT IS FOR A 27KW NATURAL GAS |
| GENERATOR. THE GENERATOR PAD SPEC SHEET IS FOR A 22KW |
| GENERATOR. PLEASE PROVIDE THE DIGITALLY SIGNED AND |
| SEALED SPEC SHEETS FOR THE 27 KW GENERATOR. FBC FS |
| 107.2.1 |
| |
| 2) THE GAS SUB PERMIT HAS BPM GAS SYSTEMS AS THE |
| CONTRACTOR, THE GAS ISOMETRIC HAS DIG IT UNLIMITED. IF |
| THE CONTRACTOR HAS CHANGED PLEASE SUBMIT A CHANGE OF |
| CONTRACTOR FORM AND FILL OUT A NEW GAS SUB PERMIT. FBC |
| FS 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |