2020-10-05 08:21:50PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE GENERATOR PAD DESIGN FOR 27KW GENERATOR.
 NOTE: 27KW GENERATOR WEIGHT IS 426 LBS. SEE PAGE 6 OF
 11 OF GENERATOR SPECS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE SITE SPECIFIC WIND DESIGN LOADS OF GENERATOR
 PER R301 OR ASCE 7-10.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
  
 2. DESIGNER TO SIGN DESIGN.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  