Plan Review Notes For Permit 20060169 |
Permit Number |
20060169 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-10-05 08:21:50 | PLAN REVIEW GENERATOR / BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE GENERATOR PAD DESIGN FOR 27KW GENERATOR. | | NOTE: 27KW GENERATOR WEIGHT IS 426 LBS. SEE PAGE 6 OF | | 11 OF GENERATOR SPECS. | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 2. PROVIDE SITE SPECIFIC WIND DESIGN LOADS OF GENERATOR | | PER R301 OR ASCE 7-10. | | R301.2.1 WIND DESIGN CRITERIA. | | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN | | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING | | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED | | FROM FIGURE R301.2(4). | | | | | | 2. DESIGNER TO SIGN DESIGN. | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | 481, F.S. & 61G1. | | | | |
|