Notes |
Date |
Text |
2020-07-07 15:41:13 | PLAN REVIEW - FUEL GAS | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE DETAIL OF GENERATOR GAS COMPONENTS. RISER, | | SHUTOFF, REGULATOR, DRIP LEG AND FLEX CONNECTOR. | | | | 2. PROVIDE APPROPRIATE TABLE FOR 2 PSI P.E. PIPE FROM | | FBC RESIDENTIAL FUEL GAS TABLES. | | | | 3. PROVIDE SPECS. FOR 2 PSI REGULATOR RATED FOR | | EXTERIOR INSTALLATION. | | | | 4. PROVIDE SPECS. FOR FLEX CONNECTOR. | | | | 5. PROVIDE TOTAL SUPPLY BTU FROM UTILITY. | | |
|