Plan Review Notes For Permit 20060136 |
Permit Number |
20060136 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-11 13:58:01 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT-20060136 | | | | CODES IN EFFECT: | | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ?EXISTING LINE? DOES NOT MATCH WPB PERMIT | | #00050189 ISSUED MAY 09 2000. FBC FS 107.2.1 | | | | 2) PLEASE PROVIDE THE GAS TABLES USED TO SIZE THIS | | PIPING SYSTEM. . FBC FS 107.2.1 | | | | 3) WHAT IS THE DISTANCE FOR THE PIPE THAT COMES FROM | | THE METER TO THE 1ST T FITTING? . FBC FS 107.2.1 | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | |
|