Plan Review Notes
Plan Review Notes For Permit 20060131
Permit Number 20060131
Review Stop B
Sequence Number 4
Notes
Date Text
2020-08-10 12:39:36WINDOWS/DOORS/SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE 10 STORY BUILDING WOULD USE A MEAN ROOF HEIGHT
 OF 120 PER THE WIND DESIGN PRESSURE CHART PROVIDED.
 2) THE SLIDING GLASS DOOR SHOWN IN WIND ZONE 5 DOES NOT
 MEET THE REQUIRED WIND PRESSURES OF (-100.9) PER THE
 CHART PROVIDED. (CANNOT USE A SHUTTER TO MAKE UP FOR
 THE REQUIRED PRESSURES ON THE DOOR)
 3) THE SHUTTER NUMBER 13 DOES NOT MEET THE REQUIRED
 WIND DESIGN PRESSURES (THERE IS NO ON CENTER SPACING
 FOR 8 FOOT SPAN, (-100.9), USING (G) AT THE TOP).
 4) SHUTTER NUMBER 1 = THE ON CENTER SPACING FOR THE (G)
 TOP SHOWN ON THE SHUTTER ATTACHMENT FORM IS INCORRECT
 (SHOULD BE 8 INCHES ON CENTER)
 5) PLEASE SHOW THE ENTIRE BUILDING LENGTH AND WIDTH -
 NEEDED TO DETERMINE WIND ZONES 4 AND 5.
 6) PLEASE UPDATE YOUR WINDOW SCHEDULE - YOU SHOW THE
 BUILDING LESS THAN 70 FEET HIGH. WIND DESIGN PRESSURES
 ARE BASED ON THE BUILDING ROOF HEIGHT (THE BUILDING
 APPEARS TO BE 10 STORIES WHICH WOULD BE APPROXAMETLY
 100 FEET HIGH).
 7) THE WIND DESIGN PRESSURE CHART NEEDS TO BE SIGNED
 ELECTRONICALLY BY THE ENGINEER - SEE FYI BELOW.
  
 THE BEST WAY TO REACH ME IS BY E MAIL (PLEASE E MAIL
 QUESTIONS TO [email protected])
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS
 MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN
 REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING
 DEPT.)