2020-08-10 12:39:36 | WINDOWS/DOORS/SHUTTERS |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) THE 10 STORY BUILDING WOULD USE A MEAN ROOF HEIGHT |
| OF 120 PER THE WIND DESIGN PRESSURE CHART PROVIDED. |
| 2) THE SLIDING GLASS DOOR SHOWN IN WIND ZONE 5 DOES NOT |
| MEET THE REQUIRED WIND PRESSURES OF (-100.9) PER THE |
| CHART PROVIDED. (CANNOT USE A SHUTTER TO MAKE UP FOR |
| THE REQUIRED PRESSURES ON THE DOOR) |
| 3) THE SHUTTER NUMBER 13 DOES NOT MEET THE REQUIRED |
| WIND DESIGN PRESSURES (THERE IS NO ON CENTER SPACING |
| FOR 8 FOOT SPAN, (-100.9), USING (G) AT THE TOP). |
| 4) SHUTTER NUMBER 1 = THE ON CENTER SPACING FOR THE (G) |
| TOP SHOWN ON THE SHUTTER ATTACHMENT FORM IS INCORRECT |
| (SHOULD BE 8 INCHES ON CENTER) |
| 5) PLEASE SHOW THE ENTIRE BUILDING LENGTH AND WIDTH - |
| NEEDED TO DETERMINE WIND ZONES 4 AND 5. |
| 6) PLEASE UPDATE YOUR WINDOW SCHEDULE - YOU SHOW THE |
| BUILDING LESS THAN 70 FEET HIGH. WIND DESIGN PRESSURES |
| ARE BASED ON THE BUILDING ROOF HEIGHT (THE BUILDING |
| APPEARS TO BE 10 STORIES WHICH WOULD BE APPROXAMETLY |
| 100 FEET HIGH). |
| 7) THE WIND DESIGN PRESSURE CHART NEEDS TO BE SIGNED |
| ELECTRONICALLY BY THE ENGINEER - SEE FYI BELOW. |
| |
| THE BEST WAY TO REACH ME IS BY E MAIL (PLEASE E MAIL |
| QUESTIONS TO [email protected]) |
| |
| FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO |
| BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. |
| DRAWINGS DO NOT SHOW IN "ADOBE READER" AS |
| DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR |
| ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG |
| WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON |
| FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS |
| MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN |
| REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING |
| DEPT.) |