2020-07-17 13:54:24 | WINDOWS/DOORS/SHUTTERS |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) BUILDING APPEARS TO BE OVER 60 FEET HIGH - THE WIND |
| DESIGN PRESSURES PROVIDED ARE FOR A BUILDING LESSTHAN |
| 60 FEET HIGH - PLEASE PROVIDE THE CORRECT SIGNED AND |
| SEALED WIND DESIGN PRESSURES FROM AN ARCHITECT OR |
| ENGINEER FOR THIS BUILDING FBC 1609. |
| 2) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION ON |
| THE UNIT WITHIN THE BUILDING - NEEDED TO DETERMINE THE |
| WIND ZONES 4 OR 5. |
| 3) IF THE UNIT IS AN END UNIT PLEASE SHOW THE DISTANCE |
| FROM THE CORNER OF THE BUILDING TO THE EDGE OF THE |
| CORNER WINDOWS OR DOORS - NEEDED TO DETERMINE IF IN |
| WIND ZONE 4 OR 5. |
| 4) PLEASE SHOW THE ENTIRE BUILDING LENGTH AND WIDTH - |
| NEEDED TO DETERMINE WIND ZONES 4 AND 5. |
| 5) PLEASE UPDATE YOUR WINDOW SCHEDULE - YOU SHOW THE |
| BUILDING LESSTHAN 55 FEET HIGH. WIND DESIGN PRESSURES |
| ARE BASED ON THE BUILDING ROOF HEIGHT (THE BUILDING |
| APPEARS TO BE 10 STORIES). |
| |
| FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO |
| BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. |
| DRAWINGS DO NOT SHOW IN "ADOBE READER" AS |
| DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR |
| ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG |
| WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON |
| FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS |
| MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN |
| REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING |
| DEPT.) |
| |
| |