Plan Review Notes
Plan Review Notes For Permit 20060037
Permit Number 20060037
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-06-04 10:51:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE ARE EXIT DOORS INDICATED, HOWEVER, THERE ARE
 NO LOCKS NOR HARDWARE INDICATED.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2 MEANS OF EGRESS COMPONENTS.
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO
 THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE
 SPECIAL
 REQUIREMENTS OF 7.2.1.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL
 BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF
 OPERATION AND THAT IS READILY OPERATED UNDER ALL
 LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE
 LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR
 OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF
 WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS
 OTHERWISE
 SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR
 7.2.1.5.10.6.
  
 PLEASSE ENSURE COMPLIANCE AS THE FIRE INSPECTOR WILL
 VERIFY AND CONFIRM INSTALLATION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  