2020-06-04 10:51:38 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) THERE ARE EXIT DOORS INDICATED, HOWEVER, THERE ARE |
| NO LOCKS NOR HARDWARE INDICATED. |
| |
| PER NFPA 101, CH 7 MEANS OF EGRESS |
| |
| 7.2 MEANS OF EGRESS COMPONENTS. |
| 7.2.1 DOOR OPENINGS. |
| 7.2.1.1 GENERAL. |
| 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL |
| CONFORM TO |
| THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE |
| SPECIAL |
| REQUIREMENTS OF 7.2.1. |
| |
| 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| READILY FROM |
| THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| TO DOOR |
| LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| ELEVATED |
| TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| LABORATORY |
| FIRE TEST PROCEDURES. |
| 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| OF A KEY, A |
| TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| THE EGRESS |
| SIDE. |
| 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| SHALL NOT |
| APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| 23. |
| 7.2.1.5.5 KEY-OPERATED LOCKS. |
| 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| PERMITTED TO HAVE |
| KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| ALL OF THE |
| FOLLOWING CRITERIA ARE MET: |
| (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| THROUGH 43 FOR |
| THE SPECIFIC OCCUPANCY. |
| (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| THAN 1 IN. |
| (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| THIS |
| DOOR TO REMAIN UNLOCKED WHEN THE |
| BUILDING IS OCCUPIED. |
| (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| DISTINGUISHABLE |
| AS LOCKED. |
| (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| INSIDE THE |
| BUILDING WHEN IT IS LOCKED. |
| |
| 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| LEAF SHALL |
| BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS |
| METHOD OF |
| OPERATION AND THAT IS READILY OPERATED UNDER ALL |
| LIGHTING CONDITIONS. |
| 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH |
| SHALL BE |
| LOCATED AS FOLLOWS: |
| (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED |
| FLOOR FOR |
| OTHER THAN EXISTING INSTALLATIONS |
| (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED |
| FLOOR |
| 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE |
| DOOR LEAF |
| WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS |
| OTHERWISE |
| SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR |
| 7.2.1.5.10.6. |
| |
| PLEASSE ENSURE COMPLIANCE AS THE FIRE INSPECTOR WILL |
| VERIFY AND CONFIRM INSTALLATION. |
| |