2020-06-19 08:45:43 | PLAN |
| REVIEW COMMENTS |
| 4TH REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING - PREVIOUS COMMENTS WERE NOT |
| ADDRESSED |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) (REPEAT COMMENT. THE WINDLOAD CALCULATIONS ARE NOT |
| DIGITALLY SIGNED.) SUBMIT REQUIRED COMPONENT AND |
| CLADDING DESIGN PRESSURES FOR THE OPENINGS THAT HAVE |
| BEEN PREPARED BY A FLORIDA LICENSED ENGINEER. THE |
| DOCUMENTS ARE REQUIRED TO BE DIGITALLY SIGNED BY THE |
| ENGINEER IF SUBMITTED ELECTRONICALLY AND THE ENGINEER'S |
| ORIGINAL HANDWRITTEN SIGNATURE IF PAPER DOCUMENTS ARE |
| SUBMITTED. FS 471 & FAC 61G15 THESE DOCUMENTS ARE |
| SUBMITTED ELECTRONICALLY, THEREFORE, THE ENGINEER IS |
| REQUIRED TO DIGITALLY SIGN THE DESIGN PRESSURE CHART. |
| |
| 2) THE DESIGN PRESSURE CAPACITY FOR THE MULLION THAT IS |
| SPECIFIED ON SHEET 5 OF 25 OF THE PRODUCT APPROVAL IS |
| 35.3 PSF. THIS IS TOO LOW. PLEASE REVISE. FBC 107 |
| ( NEW NOTE: SEE PAGES 28 AND 29 OF THE MULLION PRODUCT |
| APPROVAL. THIS IS RECTANGULAR LOADING. THE MULL LENGTH |
| IS 62 INCHES. THE OPENING WIDTH IS 36 INCHES + 36 |
| INCHES + THE MULL WIDTH = 72 + MULL WIDTH. IF THE EXACT |
| SIZES ARE NOT LISTED IN THE CHART USE THE NEXT HIGHEST. |
| THE MULL THAT IS USED IS REQUIRED TO HAVE DESIGN |
| PRESSURES THAT ARE HIGHER THAN THE PRESSURES REQUIRED |
| FOR THE OPENING. IF THE REQUIRED OPENING PRESSURES ARE |
| +65.9 PSF, -120.8 PSF THEN THE MULLION DESIGN PRESSURES |
| ARE REQUIRED TO BE GREATER THAN THAT.) |
| |