Plan Review Notes
Plan Review Notes For Permit 20060023
Permit Number 20060023
Review Stop B
Sequence Number 4
Notes
Date Text
2020-06-19 08:45:43PLAN
 REVIEW COMMENTS
 4TH REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - PREVIOUS COMMENTS WERE NOT
 ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (REPEAT COMMENT. THE WINDLOAD CALCULATIONS ARE NOT
 DIGITALLY SIGNED.) SUBMIT REQUIRED COMPONENT AND
 CLADDING DESIGN PRESSURES FOR THE OPENINGS THAT HAVE
 BEEN PREPARED BY A FLORIDA LICENSED ENGINEER. THE
 DOCUMENTS ARE REQUIRED TO BE DIGITALLY SIGNED BY THE
 ENGINEER IF SUBMITTED ELECTRONICALLY AND THE ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE IF PAPER DOCUMENTS ARE
 SUBMITTED. FS 471 & FAC 61G15 THESE DOCUMENTS ARE
 SUBMITTED ELECTRONICALLY, THEREFORE, THE ENGINEER IS
 REQUIRED TO DIGITALLY SIGN THE DESIGN PRESSURE CHART.
  
 2) THE DESIGN PRESSURE CAPACITY FOR THE MULLION THAT IS
 SPECIFIED ON SHEET 5 OF 25 OF THE PRODUCT APPROVAL IS
 35.3 PSF. THIS IS TOO LOW. PLEASE REVISE. FBC 107
 ( NEW NOTE: SEE PAGES 28 AND 29 OF THE MULLION PRODUCT
 APPROVAL. THIS IS RECTANGULAR LOADING. THE MULL LENGTH
 IS 62 INCHES. THE OPENING WIDTH IS 36 INCHES + 36
 INCHES + THE MULL WIDTH = 72 + MULL WIDTH. IF THE EXACT
 SIZES ARE NOT LISTED IN THE CHART USE THE NEXT HIGHEST.
 THE MULL THAT IS USED IS REQUIRED TO HAVE DESIGN
 PRESSURES THAT ARE HIGHER THAN THE PRESSURES REQUIRED
 FOR THE OPENING. IF THE REQUIRED OPENING PRESSURES ARE
 +65.9 PSF, -120.8 PSF THEN THE MULLION DESIGN PRESSURES
 ARE REQUIRED TO BE GREATER THAN THAT.)
  