2020-06-08 09:14:19PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - PREVIOUS COMMENTS WERE NOT
 ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT REQUIRED COMPONENT AND CLADDING DESIGN
 PRESSURES FOR THE OPENINGS THAT HAVE BEEN PREPARED BY A
 FLORIDA LICENSED ENGINEER. THE DOCUMENTS ARE REQUIRED
 TO BE DIGITALLY SIGNED BY THE ENGINEER IF SUBMITTED
 ELECTRONICALLY AND THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE IF PAPER DOCUMENTS ARE SUBMITTED. FS 471 &
 FAC 61G15 THESE DOCUMENTS ARE SUBMITTED ELECTRONICALLY,
 THEREFORE, THE ENGINEER IS REQUIRED TO DIGITALLY SIGN
 THE DESIGN PRESSURE CHART.
  
 2) THE DESIGN PRESSURE CAPACITY FOR THE MULLION THAT IS
 SPECIFIED ON SHEET 5 OF 25 OF THE PRODUCT APPROVAL IS
 35.3 PSF. THIS IS TOO LOW. PLEASE REVISE. FBC 107
  
 3) SUBMIT A RESPONSE LETTER SPECIFYING HOW EACH OF THE
 REVIEW COMMENTS HAS BEEN ADDRESSED.