2020-06-02 11:35:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT REQUIRED COMPONENT AND CLADDING DESIGN
 PRESSURES FOR THE OPENINGS THAT HAVE BEEN PREPARED BY A
 FLORIDA LICENSED ENGINEER. THE DOCUMENTS ARE REQUIRED
 TO BE DIGITALLY SIGNED BY THE ENGINEER IF SUBMITTED
 ELECTRONICALLY AND THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE IF PAPER DOCUMENTS ARE SUBMITTED. FS 471 &
 FAC 61G15
  
 2) THE DESIGN PRESSURE CAPACITY FOR THE MULLION THAT IS
 SPECIFIED ON SHEET 5 OF 25 OF THE PRODUCT APPROVAL IS
 35.3 PSF. THIS IS TOO LOW. PLEASE REVISE. FBC 107