Plan Review Notes
Plan Review Notes For Permit 20051006
Permit Number 20051006
Review Stop G
Sequence Number 1
Notes
Date Text
2020-06-18 14:38:431ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A COMPLETE CONCRETE PAD DESIGN, THE
 ONE IN THIS SUBMITTAL WAS CUT OFF AND CAN ONLY SEE HALF
 OF THE DOCUMENT. FBC FS 107.2.1
  
 2) PLEASE SHOW THE SIZE OF THE PIPE AND THE MATERIAL OF
 THE PIPE LEAVING THE METER AND SUPPLYING THE GAS LOAD
 TO THE HOUSE. FBC FS 107.2.1
  
 3) IS THE EXISTING GAS SERVICE A 2 PSI SYSTEM? IF SO,
 PLEASE SHOW THE MP REGULATOR FOR THE APPLIANCES. FBC FS
 107.2.1
  
 4) WHAT TYPE OF CONNECTION IS BEING USED BETWEEN THE PE
 PIPING AND THE GENERATOR? IF A HOSE IS USED PLEASE
 PROVIDE THE SPECS AND IDENTIFY THE HOSE USED. PLEASE
 SHOW PRESSURE DROP.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  