2020-06-18 14:38:43 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT |
| |
| CODES IN EFFECT: |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE A COMPLETE CONCRETE PAD DESIGN, THE |
| ONE IN THIS SUBMITTAL WAS CUT OFF AND CAN ONLY SEE HALF |
| OF THE DOCUMENT. FBC FS 107.2.1 |
| |
| 2) PLEASE SHOW THE SIZE OF THE PIPE AND THE MATERIAL OF |
| THE PIPE LEAVING THE METER AND SUPPLYING THE GAS LOAD |
| TO THE HOUSE. FBC FS 107.2.1 |
| |
| 3) IS THE EXISTING GAS SERVICE A 2 PSI SYSTEM? IF SO, |
| PLEASE SHOW THE MP REGULATOR FOR THE APPLIANCES. FBC FS |
| 107.2.1 |
| |
| 4) WHAT TYPE OF CONNECTION IS BEING USED BETWEEN THE PE |
| PIPING AND THE GENERATOR? IF A HOSE IS USED PLEASE |
| PROVIDE THE SPECS AND IDENTIFY THE HOSE USED. PLEASE |
| SHOW PRESSURE DROP. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |