Plan Review Notes
Plan Review Notes For Permit 20051001
Permit Number 20051001
Review Stop G
Sequence Number 1
Notes
Date Text
2020-06-17 15:33:281ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20051001
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD THE VALUE OF THIS PROJECT TO THE GAS SUB
 PERMIT. FBC FS 107.2.1
  
 2) INTERIOR IS EXISTING LOW PRESSURE SYSTEM, THE METER
 IS GOING TO BE UPGRADED TO A 2PSI SYSTEM. WHERE IS THE
 MP REGULATOR FOR THE INTERIOR PIPING SYSTEM MAKING IT A
 LOW PRESSURE SYSTEM? FBC FS 107.2.1
  
 3) HOW IS THE ?? PE PIPING CONNECTING TO THE GENERATOR?
 IF A HOSE IS TO BE USED FOR THIS CONNECTION, PLEASE
 PROVIDE SPEC SHEETS FOR THIS HOSE. PLEASE IDENTIFY
 WHICH HOSE IS TO BE USED ALONG WITH THE PRESSURE DROP.
 FBC FS 107.2.1
  
 4) PROVIDE A DETAIL DRAWING OF THE NEW METER WITH THE
 2PSI REGULATOR AND THE PIPING TO THE BRANCHES TO THE
 GENERATOR, THE FUTURE POOL AND THE EXISTING HOUSE LOW
 PRESSURE SYSTEM. PLEASE SHOW PIPE SIZES, REGULATOR AND
 FITTINGS . FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  