2020-06-17 14:18:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT -20050999
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE SPEC SHEETS FOR THE REGULATORS. FBC FS
 107.2.1
  
 2) THE INTERIOR GAS SYSTEM IS A LOW PRESSURE SYSTEM,
 THE NEW REGULATOR AT THE METER IS A 2PSI REGULATOR
 MAKING THIS ENTIRE SYSTEM A 2PSI SYSTEM. WHERE IS THE
 MP REGULATOR FOR THE INTERIOR GAS SYSTEM? AGAIN, THE
 REGULATOR AT THE METER IS 2 PSI. WHY IS THERE ANOTHER
 2PSI REGULATOR AT THE NEW GENERATOR? SHOULDN?T THIS BE
 AN MP REGULATOR? PLEASE PROVIDE THE GAS TABLES USED FOR
 BOTH THE LOW PRESSURE AND 2PSI SYSTEMS. FBC FS 107.2.1
  
 3) HOW IS THE GENERATOR BEING CONNECTED TO THE ?? PE?
 IF A FLEXIBLE HOSE IS TO BE USED PLEASE SUPPLY SPECS.
 FOR THE HOSE AND LABEL THE HOSE TO BE USED ON THE SPEC
 SHEET ALONG WITH THE PRESSURE DROP. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  