2020-07-30 16:59:42 | 07/30/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. |
| |
| 2. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT |
| INSTALLED IF INSIDE GENERATOR MAKE NOTE PER THE 2017 |
| FBC RES. SEC. G2419.2. |
| |
| 3. PLEASE SHOW THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| THE 2017 FBC FG SEC. 409.4 OR 2017 FBC RES. SEC. |
| G2401.1.3. |
| |
| 4. PLEASE SHOW AND LABEL THE REGULATOR ON GAS ISOMERIC |
| PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC RES. SEC. |
| G2401.1.3. |
| |
| 5. PLEASE SHOW THE PE LINES ON THE SIDE OF EXIT ON THE |
| METER NOT THE INLET PER THE WPB AMENDMENTS TO THE FBC |
| SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 6. THE GENERATOR ON THE ISOMETRIC SAYS 27 KW, PLEASE |
| CHANGE TO BTU'S AND BELOW YOU HAVE 330 BTU'S WHICH AT |
| FULL LOAD A 27 KW SHOULD BE 359 BTU'S SO RECALCULATE |
| AND CHANGE TOTAL BTU'S PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM |
| [email protected] |
| 561-701-6437 |
| |