2020-06-12 14:55:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050996
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) . THIS SUBMISSION DOES NOT SHOW ANY EXISTING GAS
 LINE FOR THIS PROJECT. PLEASE PROVIDE A COMPLETE GAS
 LINE DIAGRAM SHOWING ALL THE EXISTING APPLIANCES AND
 GAS LINES. INCLUDE PIPE MATERIAL AND PIPE SIZES ALONG
 WITH ANY REGULATORS AND GAS PRESSURES FOR THE ENTIRE
 SYSTEM. PLEASE SHOW A DETAIL OF THE CONNECTION OF THE
 NEW GAS LINE FOR THE GENERATOR TO THE EXISTING GAS
 LINE.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  