Plan Review Notes For Permit 20050996 |
Permit Number |
20050996 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-12 14:55:47 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20050996 | | | | CODES IN EFFECT: | | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) . THIS SUBMISSION DOES NOT SHOW ANY EXISTING GAS | | LINE FOR THIS PROJECT. PLEASE PROVIDE A COMPLETE GAS | | LINE DIAGRAM SHOWING ALL THE EXISTING APPLIANCES AND | | GAS LINES. INCLUDE PIPE MATERIAL AND PIPE SIZES ALONG | | WITH ANY REGULATORS AND GAS PRESSURES FOR THE ENTIRE | | SYSTEM. PLEASE SHOW A DETAIL OF THE CONNECTION OF THE | | NEW GAS LINE FOR THE GENERATOR TO THE EXISTING GAS | | LINE. | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|