2020-06-11 13:48:52 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SIGNED AND SEALED WINDLOAD CALCULATIONS ONLY | | LIST THE TWO LARGER OPENINGS. THE TWO SMALLER OPENINGS | | WITH THE HIGHER COMPONENT AND CLADDING PRESSURES ARE | | NOT LISTED. FBC 107 |
|