2020-06-08 11:36:47ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOFING PRODUCT APPROVAL NEEDS TO BE REVIEWED AND
 MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD.
 2) PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 PRODUCT APPROVAL.
 3) PROVIDE ADDITIONAL SIGNED AND SEALED ATTACHMENT
 DETAILS FROM AN ARCHITECT OR ENGINEER FOR ROOFING ZONES
 2 AND 3 THAT MAY REQUIRE HIGHER PRESSURES THAN THE
 MAXIMUM PRESSURE SHOWN ON THE ROOFING SYSTEM TO BE
 INSTALLED AS YOU CIRCLED ON THE PRODUCT APPROVAL.
 SIGNED AND SEALED ATTACHMENT DETAILS NEED TO BE
 ELECTRONICALLY/DIGITALLY SIGNED AND SEALED TO BE USED
 IN ELECTRONIC PLAN REVIEW.
  