Plan Review Notes For Permit 20050956 |
Permit Number |
20050956 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-08 13:46:46 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20050956 | | | | CODES IN EFFECT: | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE UPLOAD THE PERMIT APPLICATIONS FOR THIS | | PROJECT. FBC FS 107.2.1 | | | | 2) PLEASE PROVIDE THE SPECS FOR THE RANGE AND SHOW THAT | | IT IS SUITED FOR A RESIDENTIAL INSTALLATION. FBC RES | | M1901.2 | | | | 3) PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR THIS | | RANGE IN THIS SPACE. FBC RES G2407.5 | | | | 4) PLEASE PROVIDE HOOD SPECS FOR THE HOOD RECOMMENDED | | FOR THIS RANGE. FBC RES M1503.4 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|