2020-06-12 11:55:27 | PLAN REVIEW - FUEL GAS |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. SEPERATE GAS PERMIT REQUIRED. |
| PERMITS |
| 105.1 REQUIRED. |
| |
| 2. PROVIDE GAS PLAN. |
| 107.2 CONSTRUCTION DOCUMENTS. |
| |
| 3. PROVIDE GAS RISER DIAGRAHM. |
| EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL |
| BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING |
| IN THE CITY OF WEST PALM BEACH: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-R SEC. |
| G2413.4.1, G2413.4.2. |
| |
| 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING |
| |
| (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO |
| FBC SEC.107.2.1. |
| |
| 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| |
| 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-RES. SEC. |
| G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH |
| G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES ARE |
| USED. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| FBC-RES. SEC. G 2413.4.1, G2413.4.2. |
| |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS). |
| |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| |
| 8. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION, |
| SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND |
| ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-RES. |
| SEC.G2426 THROUGH G2439. |
| |
| 9. SUBMIT A COPY OF THE MANUFACTURER?S SPECIFICATION |
| SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FBC-RES. SEC.G2408.1. |
| |
| |
| |
| |