Plan Review Notes
Plan Review Notes For Permit 20050937
Permit Number 20050937
Review Stop B
Sequence Number 1
Notes
Date Text
2020-06-02 13:18:50BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 20050937
 REVIEWED: JUNE 2, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 1816.1 FBC[B] TERMITE PROTECTION. TERMITE PROTECTION
 SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING
 SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS
 OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202,
 ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE
 APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE
 BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
 - ADD NOTES TO SHOW COMPLIANCE WITH 1816.1 FBC[B]
 TERMITE PROTECTION.
  
 2) 1203.4 UNDER-FLOOR VENTILATION. THE SPACE BETWEEN
 THE BOTTOM OF THE FLOOR JOISTS AND THE EARTH UNDER ANY
 BUILDING EXCEPT SPACES OCCUPIED BY BASEMENTS OR CELLARS
 SHALL BE PROVIDED WITH VENTILATION OPENINGS THROUGH
 FOUNDATION WALLS OR EXTERIOR WALLS. SUCH OPENINGS SHALL
 BE PLACED SO AS TO PROVIDE CROSS VENTILATION OF THE
 UNDER-FLOOR SPACE.
  
 3) 1203.4.1 OPENINGS FOR UNDER-FLOOR VENTILATION. THE
 NET AREA OF VENTILATION OPENINGS SHALL BE NOT LESS THAN
 1 SQUARE FOOT FOR EACH 150 SQUARE FEET (0.67 M2 FOR
 EACH 100 M2) OF CRAWL-SPACE AREA. VENTILATION OPENINGS
 SHALL BE COVERED FOR THEIR HEIGHT AND WIDTH WITH ANY OF
 THE FOLLOWING MATERIALS, PROVIDED THAT THE LEAST
 DIMENSION OF THE COVERING SHALL BE NOT GREATER THAN 1/4
 INCH (6.4 MM):
 - PLEASE PROVIDE THE CALCULATION, SIZE AND AMOUNT OF
 VENTS.
  
 4) 1609.4.3 FBC(B) EXPOSURE CATEGORIES. THIS SITE WOULD
 BE EXPOSURE "C" SINCE IT DOESN?T MEET THE CRITERIA FOR
 EXPOSURE B OR D. IF YOU USE A MORE STRINGENT CATEGORY
 NOW WE WILL USE IT FOR ALL WINDOW AND DOOR CALCULATIONS
 AND A HIGHER PRESUURE THAN NEEDED WILL BE APPLIED.
 -PLEASE ADJUST TO CATEGORY C OR STATE THAT YOU WOULD
 LIKE TO EXCEED CODE MINIMUM.
  
 PROVISOS:
 DEFERRED SUBMITTALS-
 COMPONENT AND CLADDING WITH INTERIOR BUILD-OUT
 SEPARATE PERMITS REQUIRED FOR-
 INTERIOR BUILD-OUT, LIGHT POLES/SITE LIGHTING, FIRE
 ALARM, LOW VOLTAGE, ACCESS, LANDSCAPING, IRRIGATION,
 PARKING LOT.
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
 - PROVISOS WILL BE ADDED TO THE PLANS PRIOR TO
 ISSUANCE. IF YOU SEE SOME THAT DON'T APPLY PLEASE
 INDICATE IN YOUR COMMENT RESPONSE AND I WILL ADJUST.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  