2020-06-02 13:18:50 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 20050937 |
| REVIEWED: JUNE 2, 2020 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| BELOW) |
| HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| BUILDING-PERMIT-FORMS |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| 1) 1816.1 FBC[B] TERMITE PROTECTION. TERMITE PROTECTION |
| SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING |
| SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND |
| PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS |
| OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE |
| TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202, |
| ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE |
| APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A |
| CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE |
| BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL |
| COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE |
| BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE |
| PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN |
| ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE |
| FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER |
| SERVICES.? |
| - ADD NOTES TO SHOW COMPLIANCE WITH 1816.1 FBC[B] |
| TERMITE PROTECTION. |
| |
| 2) 1203.4 UNDER-FLOOR VENTILATION. THE SPACE BETWEEN |
| THE BOTTOM OF THE FLOOR JOISTS AND THE EARTH UNDER ANY |
| BUILDING EXCEPT SPACES OCCUPIED BY BASEMENTS OR CELLARS |
| SHALL BE PROVIDED WITH VENTILATION OPENINGS THROUGH |
| FOUNDATION WALLS OR EXTERIOR WALLS. SUCH OPENINGS SHALL |
| BE PLACED SO AS TO PROVIDE CROSS VENTILATION OF THE |
| UNDER-FLOOR SPACE. |
| |
| 3) 1203.4.1 OPENINGS FOR UNDER-FLOOR VENTILATION. THE |
| NET AREA OF VENTILATION OPENINGS SHALL BE NOT LESS THAN |
| 1 SQUARE FOOT FOR EACH 150 SQUARE FEET (0.67 M2 FOR |
| EACH 100 M2) OF CRAWL-SPACE AREA. VENTILATION OPENINGS |
| SHALL BE COVERED FOR THEIR HEIGHT AND WIDTH WITH ANY OF |
| THE FOLLOWING MATERIALS, PROVIDED THAT THE LEAST |
| DIMENSION OF THE COVERING SHALL BE NOT GREATER THAN 1/4 |
| INCH (6.4 MM): |
| - PLEASE PROVIDE THE CALCULATION, SIZE AND AMOUNT OF |
| VENTS. |
| |
| 4) 1609.4.3 FBC(B) EXPOSURE CATEGORIES. THIS SITE WOULD |
| BE EXPOSURE "C" SINCE IT DOESN?T MEET THE CRITERIA FOR |
| EXPOSURE B OR D. IF YOU USE A MORE STRINGENT CATEGORY |
| NOW WE WILL USE IT FOR ALL WINDOW AND DOOR CALCULATIONS |
| AND A HIGHER PRESUURE THAN NEEDED WILL BE APPLIED. |
| -PLEASE ADJUST TO CATEGORY C OR STATE THAT YOU WOULD |
| LIKE TO EXCEED CODE MINIMUM. |
| |
| PROVISOS: |
| DEFERRED SUBMITTALS- |
| COMPONENT AND CLADDING WITH INTERIOR BUILD-OUT |
| SEPARATE PERMITS REQUIRED FOR- |
| INTERIOR BUILD-OUT, LIGHT POLES/SITE LIGHTING, FIRE |
| ALARM, LOW VOLTAGE, ACCESS, LANDSCAPING, IRRIGATION, |
| PARKING LOT. |
| CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| SAT-SUN |
| - PROVISOS WILL BE ADDED TO THE PLANS PRIOR TO |
| ISSUANCE. IF YOU SEE SOME THAT DON'T APPLY PLEASE |
| INDICATE IN YOUR COMMENT RESPONSE AND I WILL ADJUST. |
| |
| NOTES: |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |