2020-06-08 17:34:09 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20050909 |
| ADD: 1845 PALM BEACH LAKES BLVD. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: ??? |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: MON. JUNE 08/2020 |
| ACTION: DENIED |
| |
| 1) SHEET S.001 IS SILENT AS TO HOW THE TERMITE |
| TREATMENT (2017 FBC-B 1816.1) OF THE FLOOR SLAB BOTH |
| INSIDE AND OUT HOW CODE COMPLIANCE WILL BE ACHIEVED. |
| THE SHEET S.001 NEITHER INDICATES THE VAPOR / MOISTURE |
| BARRIER REQUIRED BY 1816.1.4. |
| |
| 2) SHEET S.001 DETAIL # 1 SHOWS THE NEW DOOR OPENING |
| THE SAME WIDTH AS THE OLD WINDOW, NO WIDTH IS GIVEN. |
| SHEET A012 THE ENLARGED DETAIL # 5 SHOWS THERE APPEARS |
| TO BE A FRAMED INFILL PORTION OF THE WALL BEFORE THE |
| DOOR JAMB AND DOOR. THERE IS NO INFORMATION AS TO HOW |
| THE INFILL WALL WILL BE ANCHORED, FRAMED NOR SHEATHING |
| OR FINISHES. 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA |
| FOR COMMERCIAL BUILDINGS. |
| |
| 3) SHEET S.001 DOES PROVIDE A PORTION OF THE WIND |
| DESIGN CRITERIA BUT NOT THE PRESSURES +/- FOR THE NEW |
| DOOR OPENING. PLEASE PROVIDE THE WIND DESIGN CRITERIA |
| FOR THIS STRUCTURE. 2017 FBC-B 1603.1.4 WIND DESIGN |
| DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 3.1.COMPLIED. ULTIMATE DESIGN WIND SPEED, VULT, |
| (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND |
| SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 3.2. COMPLIED. RISK CATEGORY. |
| |
| 3.3. COMPLIED. WIND EXPOSURE. APPLICABLE WIND DIRECTION |
| IF MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE |
| 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| |
| 3.4. COMPLIED. APPLICABLE INTERNAL PRESSURE |
| COEFFICIENT. |
| |
| 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE BUILDING |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 4) PLEASE SUBMIT THE PRODUCT APPROVALS FOR THE NEW |
| DOOR. 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| 5) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6) THE PLANS ARE SILENT AS TO IF THE NEW GLAZED DOOR IS |
| SOLID OR A STOREFRONT PRODUCT APPROVAL. IDENTIFY |
| GLAZING. PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 7) 2017 FBC-ACCESS. CODE. THRESHOLDS ACCESS. CODE |
| 404.2.5. THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE |
| 1/2 INCH (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND |
| CHANGES IN LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND |
| 303. |
| |
| 8A) SHEET A012 THE DETAIL 5 IT APPEARS WITH THE NEW |
| INFILL WALL FROM THE LATCH EDGE SIDE OF THE DOOR TO THE |
| NEW CURB THAT RUNS 90 DEGREES AWAY FROM THE BUILDING IT |
| APPEARS THERE IS NOT 18 INCHES CLEARANCE. |
| FBC- ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. |
| DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND |
| GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES |
| SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE |
| REQUIRED LATCH SIDE FOR SIDE CLEARANCE. SEE FIGURE |
| 404.2.1(A). |
| |
| 8B) SINCE THERE ARE NO DIMENSIONS ON SHEET A012 DETAIL |
| 5 IT CANNOT BE DETERMINED IF THERE IS AN ISSUE WITH THE |
| 2017 ACCESSIBILITY CODE SECTION 404.2.4.3. RECESSED |
| DOORS. |
| |
| 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF THE |
| COVID 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL |
| NUMBER IS 561-718-9724. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |