2020-06-08 16:23:42 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20050893 |
| ADD: 2995 45TH ST. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: ??? |
| E-MAIL: ??? |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: MON. JUNE 08/2020 |
| ACTION: DENIED |
| |
| |
| 1) SUBMITTED ARE 31 PAGES OF VARIOUS DETAILS BUT NONE |
| OF THE DETAILS SHOW A FLOOR PLAN NOR ELEVATION PLAN OF |
| THE DUMPSTER WITH CUT SECTIONS THROUGH THE FOUNDATION |
| AND SLAB NOR THROUGH THE WALL OF THE DUMPSTER. NO |
| ARCHITECTURAL NOR STRUCTURAL SHEETS. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATIVE CODE 107.3.5 MINIMUM |
| PLAN REVIEW CRITERIA FOR BUILDINGS/ STRUCTURES. |
| 107.3.5.1. COMMERCIAL BUILDINGS. |
| 107.3.5.1.1. BUILDINGS. |
| FLOOR PLAN ELEVATIONS WITH CUT SECTIONS THROUGH THE |
| SLAB AND FOUNDATION. |
| ELEVATIONS OF THE SIDE WALLS, ALSO SHOW COMPLIANCE WITH |
| CUT SECTIONS OF THE WALLS PROVIDING |
| COMPONENTS OF THE MAIN WIND FORCE RESISTING SYSTEMS. |
| FROM FOOTER TO THE TOP OF THE EITHER BOND BEAM OR |
| POURED BEAM. |
| PLEASE PROVIDE A ELEVATION OF THE GATE WAY AND PROVIDE |
| THE CLEAR WIDTH OF THE OPENING. |
| |
| 2) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THIS |
| STRUCTURE. 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 2.2. RISK CATEGORY. |
| |
| 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| |
| 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE BUILDING |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE |
| TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |