Plan Review Notes
Plan Review Notes For Permit 20050889
Permit Number 20050889
Review Stop P
Sequence Number 2
Notes
Date Text
2020-08-31 14:48:131) SHT. A3.5 - THERE IS A NOTE UNDER THE FIXTURE COUNT
 TABLE THAT STATES" A BEVERAGE FOUNTAIN WITH DRINKING
 WATER OFFERING IS USED TO SATISFY THE DRINKING FOUNTAIN
 REQUIREMENT." REMOVE THIS NOTE FROM THE PLAN AS IT DOES
 NOT MEET THE REQUIREMENT FOR DRINKING FOUNTAINS. 2ND
 REQUEST.
 2) SHT. SD2 - GREASE INTERCEPTOR DETAIL - SHOW THE
 HEIGHT OF THE TEE MANIFOLD AND VENT SLEEVE FROM THE
 FLOOR OF THE INTERCEPTOR. THE DETAIL SHOWS 0.6-0.7 FL1.
 I HAVE NO IDES WHAT THIS MEANS. SHOW THE DIMENSION IN
 INCHES.WPB AMEND.TO FBC SEC. 107.2.1.
 3) SHT. C8 REFERS TO SHT. C8.3 FOR A DETAIL FOR A 3/4
 INCH BACKFLOW DETAIL. THERE IS NO SUCH DETAIL ON SHT.
 C8.3. IN ADDITION, THE REFERENCED WILKINS 975 XL IS NOT
 A LEAD FREE DEVICE AS REQUIRED BY THE CITY OF WPB
 CROSS-CONNECTION CONTROL MANUAL.
 4) SHT. P2.2 - SHOWS A HOUSE TRAP ON THE GREASE WASTE
 SYSTEM. HOUSE TRAPS ARE PROHIBITED PER FBC-PLUMBING
 SEC.1002.6.
 5) SHT. P2.2 - IDENTIFY THE STANDARD THAT WAS USED IN
 THE SIZING CALCULATIONS FOR THE GREASE TRAP.
 6) SHT. SD2 - GREASE TRAP CALCULATIONS - THE
 CALCULATIONS SHOW 128.16 GPM FLOW RATE AND ALSO 144.68
 GPM. CLARIFY. ALSO, WHAT IS THE 7 MINUTE TIME THAT IS
 IN THE EQUATION? PLEASE EXPLAIN THESE CALCULATIONS. WPB
 AMEND TO FBC SEC. 107.2.1.
 7) SHT. IP 200 - DETAIL #10 - THE BACKFLOW DEVICE SHALL
 BE LOCATED A MINIMUM OF 18 INCHES ABOVE FINISH GRADE TO
 THE RELIIEF PORT, NOT TO THE BODY OF THE VALVE AS SHOWN
 PER CITY OF WPB CROSS-CONNECTION CONTROL MANUAL.
 8) SHT.P2.2 - DRAINS FROM THE ICE MAKERS ARE SHOWN
 DISCHARGING TO THE GREASE WASTE SYSTEM. IF THIS IS
 CLEAR WATER WASTE, IT CANNOT DISHARGE TO THE GREASE
 WASTE SYSTEM. FBC-PLUMBING SEC.1003.2.
 9) SHT. P2.2 SHOWS A 1/2 INCH LINE FROM A ROOF HYDRANT
 DISCHARGING TO THE GREASE WASTE SYSTEM. WHY IS THIS
 DISCHARGING TO THE GREASE WASTE SYSTEM? CLARIFY.
 10) THE RESPONSE NARRATIVE STATES THAT THE WASTE FROM
 THE COLD PAN (COFFEE), COLD PAN (HOT DOG), SANDWICH
 COOLERS, BILLET IMPULSE COOLER, COUNTER DRAINS, AND
 YOGURT TABLE WILL BE CONDENSATE. SOME OF THESE DRAINS
 ARE DISCHARGING TO THE SANITARY AND SOME ARE GOING TO
 THE GREASE WASTE SYSTEM. CONDENSATE SHALL NOT DISCHARGE
 TO THE GREASE WASTE SYSTEM PER FBC- PLUMBING SEC.
 1003.2.
 11) UNCONTAMINATED COOLING WATER OR AIR CONDITIONING
 CONDENSATE SHALL NOT DISCHARGE TO THE SANITARY SYSTEM
 UNLESS SPECIFICALLY AUTHORIZED BY THE CITY IN WRITING
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES CHAPTER
 90, ARTICLE III, SEC. 90-126 (B) (5).
 12) SHT. P3.2 WATER MANIFOLD/FILTER DETAIL - THERE IS A
 NOTE STATING THE A BACKFLOW PREVENTION DEVICE IS
 INSTALLLED IN A BOX AT STREET. CLARIFY. BACKFLOW
 DEVICES ARE NOT PERMITTED TO BE INSTALLED BELOW GRADE
 PER THE CITY OF WEST PALM BEACH CROSS CONNECTION
 CONTROL MANUAL.
 13) SHT. P3.2 - INDICATE THE TYPE OF BACKFLOW DEVICE ON
 THE WATER BOOSTER. THE ISOMETRIC DRAWING NOTES "CHECK
 VALVE. TYPICAL."
 14) IF THE HOSE REEL AND RINSE-O-MMATIC HAVE HOSE
 CONNECTIONS, THE TYPE OF BACKFLOW DEVICE SHALL BE A
 VACUUM BREAKER COMPLYING WITH ASSE 1011 PER
 FBC-PLUMBING TABLE 608.1.
 15) SHT. P3.1 - NOTE #17 - THE HAND SINKS SHALL HAVE
 HOT WATER PER FBC-PLLUMBING SEC.607.1. PUBLIC
 LAVATORIES SHALL HAVE TEMPERED WATER PER FBC-PLUMBING
 SEC.416..5.
 16) SHT. A10.1 - ROOF VENT NOTES - THE PLUMBING VENT
 SHALL BE AT LEAST 3 FEET OR MORE ABOVE THE TOP OF THE
 OPENING, NOT 2 FEET AS NOTED. REVISE THE NOTE.
 FBC-PLUMBING SEC.903.5.
 17) SHT. P4.1 - THIS PLAN IS NOT DIGITALLY SIGNED OR
 SEALED PER FL. ADMIN. CODE RULE 61G15-23.004,
 61G15-23.005.
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  