2020-07-06 15:37:28 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050889 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE VENTILATION CALCULATIONS. FBC M TABLE |
| 403.3.1.1 |
| |
| 2) PROVIDE SPEC SHEETS FOR EACH RTU. FBC FS 107.2.1 |
| |
| 3) PLEASE PROVIDE SPEC SHEETS FOR THE BATH EXHAUST |
| FANS. FBC FS 107.2.1 |
| |
| 4) PLEASE PROVIDE SPEC SHEETS FOR ALL COOKING |
| EQUIPMENT. FBCFS 107.2.1 |
| |
| 5) ALL WALK IN FREEZERS, COOLERS AND REFRIGERATION MUST |
| BE SUBMITTED IN ANOTHER SUBMITTAL AND PERMITTED |
| SEPARATELY. PLEASE INCLUDE ALL SPEC. SHEETS FOR EACH |
| PIECE OF EQUIPMENT AND REFRIGERATION CALCULATIONS AT |
| THAT TIME. FBC FS 107.2.1 |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |