Plan Review Notes
Plan Review Notes For Permit 20050889
Permit Number 20050889
Review Stop E
Sequence Number 1
Notes
Date Text
2020-07-07 11:48:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E5.1 1200 AMPERE MAIN IN MDP TO MEET THE
 REQUIREMENTS OF 240.87(A)(B) PLEASE SHOW ON DRAWINGS
 HOW TO ACHIEVE .
  
 FAULT CURRENT CALCULATION AND LABEL REQUIREMENTS NOT
 SHOWN ON PLANES. 110.9, 110.10, 110.24