Plan Review Notes For Permit 20050866 |
Permit Number |
20050866 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-02 16:43:21 | WINDOWS AND DOORS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE PROVIDE DIGITALLY SIGNED AND SEALED WIND | | DESIGN PRESSURES FROM AN ARCHITECT OR ENGINEER FBC 1609 | | 2) PRODUCT APPROVAL 14-0916.11 HAS EXPIRED. | | 3) PRODUCT APPROVAL FL13574-R4 = PLEASE PROVIDE THE | | INSTALLATION INSTRUCTIONS. | | 4) PLEASE SHOW THE DISTANCE FROM THE EDGE OF THE | | WINDOWS OR DOORS TO THE CORNER OF THE BUILDING = TO | | DETERMINE IF THE WINDOW OR DOOR IS IN A WIND ZONE 4 OR | | 5. |
|