Plan Review Notes For Permit 20050859 |
Permit Number |
20050859 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-02 10:56:42 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE DRAWING DOES NOT HAVE THE ADDRESS OF THE PROJECT | | AND DOES NOT SPECIFY THE REQUIRED DESIGN PRESSURES. THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE IS | | REQUIRED ON THE DRAWING. FBC 107 | | | | 2) THE TABLES IN THE PRODUCT APPROVALS FOR THE SINGLE | | HUNG WINDOW AND THE FIXED GLASS WINDOW HAVE NOT BEEN | | MARKED TO SPECIFY WHICH SIZE, GLASS TYPE AND DESIGN | | PRESSURES ARE APPLICABLE. FBC 107 | | | | 3) THE ITEMS THAT WERE MARKED IN THE TABLES FOR THE | | MULLION HAD THE WRONG OPENING HEIGHT AND DESIGN | | PRESSURES. I MARKEDUP THE CORRECT ONES. FBC 107 |
|