Notes |
Date |
Text |
2020-09-16 08:29:39 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT-20050839 | | | | CODES IN EFFECT: | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE SHOW RETURN AIR PATH FOR THE PROPOSED FAMILY | | ROOM. FBC FS 107.2.1 | | | | 2) PLEASE SHOW THE RETURN AIR IS A BALANCED. MAKE SURE | | THE RETURN AIR DUCTS ARE 1 ? TIMES THE CROSS SECTIONAL | | AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE | | ROOM. FBC RES M1602.3 | | | | 3) PLEASE PROVIDE DISTANCE OF RETURN AIR GRILL TO | | COOKING APPLIANCE IN THE KITCHEN. FBC RES M1602.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|