Plan Review Notes
Plan Review Notes For Permit 20050839
Permit Number 20050839
Review Stop M
Sequence Number 1
Notes
Date Text
2020-07-15 09:34:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050839
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PLEASE PROVIDE THE ENERGY CALCS AND THE
 MANUAL J FOR THE NEW MECHANICAL SYSTEM. FBC EC
 101.5.1.1.2
  
 2) PLEASE SHOW RETURN AIR PATH FOR THE PROPOSED FAMILY
 ROOM. FBC RES M1602.3
  
 3) PLEASE SHOW TERMINATION FOR THE DRYER DUCT. PLEASE
 PROVIDE THE DEVELOPED LENGTH OF THE DRYER DUCT. FBC FS
 107.2.1
  
 4) PLEASE PROVIDE INFORMATION FOR THE BATH EXHAUST FANS
 AND THE LOCATION OF EXTERIOR TERMINATION. FBC FS
 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved