2020-07-15 09:34:29 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050839 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-1: PLEASE PROVIDE THE ENERGY CALCS AND THE |
| MANUAL J FOR THE NEW MECHANICAL SYSTEM. FBC EC |
| 101.5.1.1.2 |
| |
| 2) PLEASE SHOW RETURN AIR PATH FOR THE PROPOSED FAMILY |
| ROOM. FBC RES M1602.3 |
| |
| 3) PLEASE SHOW TERMINATION FOR THE DRYER DUCT. PLEASE |
| PROVIDE THE DEVELOPED LENGTH OF THE DRYER DUCT. FBC FS |
| 107.2.1 |
| |
| 4) PLEASE PROVIDE INFORMATION FOR THE BATH EXHAUST FANS |
| AND THE LOCATION OF EXTERIOR TERMINATION. FBC FS |
| 107.2.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |