2020-06-05 13:43:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050817
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A GAS LINE DIAGRAM SHOWING THE
 EXISTING PIPING, THE SHUT OFFS AND THE REGULATOR USED.
 PLEASE ALSO PROVIDE THE SPECS AND MODEL NUMBER FOR THE
 REGULATOR USED. ALSO PLEASE REMEMBER THIS IS A SINGLE
 FAMILY RESIDENCE SO THE GAS TABLES FROM THE 2017
 FLORIDA RESIDENTIAL BUILDING CODE SHALL BE USED. FBC FS
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  