2020-05-29 08:55:30 | 1) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| 2) EXISTING GAS PLANS ON FILE WITH THE CITY SHOW THE |
| LONGEST RUN AS 140 FEET TO THE MOST REMOTE OUTLET BUT |
| THE SUBMITTED GAS PLAN SHOWS ONLY ONE RUN AT 45 FEET. |
| CLARIFY. |
| 3) SHOW THE TYPE OF PIPE AND THE SIZE OF THE PIPE AT |
| THE OUTLET (CONSUMER SIDE) OF THE GAS METER. THIS LINE |
| SHALL BE SIZED FOR THE TOTAL BTU LOAD ON THE SYSYTEM |
| AND THE TYPE OF PIPE. |
| 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| GENERATOR. FBC-FUEL GAS SEC.305.1. |
| |