Plan Review Notes
Plan Review Notes For Permit 20050794
Permit Number 20050794
Review Stop G
Sequence Number 1
Notes
Date Text
2020-05-29 08:55:301) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 2) EXISTING GAS PLANS ON FILE WITH THE CITY SHOW THE
 LONGEST RUN AS 140 FEET TO THE MOST REMOTE OUTLET BUT
 THE SUBMITTED GAS PLAN SHOWS ONLY ONE RUN AT 45 FEET.
 CLARIFY.
 3) SHOW THE TYPE OF PIPE AND THE SIZE OF THE PIPE AT
 THE OUTLET (CONSUMER SIDE) OF THE GAS METER. THIS LINE
 SHALL BE SIZED FOR THE TOTAL BTU LOAD ON THE SYSYTEM
 AND THE TYPE OF PIPE.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR. FBC-FUEL GAS SEC.305.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  