Plan Review Notes For Permit 20050786 |
Permit Number |
20050786 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-05-28 10:09:13 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) INDICATE THE SYSTEM NUMBER AND THE MAXIMUM DESIGN | | PRESSURE FROM THE TABLES IN THE MODIFIED BITUMEN | | ROOFING PRODUCT APPROVAL. IF THE MAXIMUM DESIGN | | PRESSURE IS LESS THAN REQUIRED FOR THE PERIMETER AND | | CORNER AREAS IN EXPOSURE C IN A 170 MPH WINDSPEED | | (-95.7PSF FOR 15' MRH), THEN YOU WILL HAVE TO SUBMIT | | SIGNED AND SEALED ENHANCED FASTENING CALCULATIONS. FBC | | 107.2.1 | | | | 2) INDICATE THE MINIMUM ATTACHMENT RESISTANCE FOR THE | | ROOF TILE BY MARKING THE APPLICABLE ITEMS IN TABLE 5 OR | | 6 OF THE PRODUCT APPROVAL. FBC 107.2.1 | | | | 3) MARK THE APPLICABLE TILE PROFILE AND ADHESIVE | | PLACEMENT DETAIL ON THE TILE ADHESIVE PRODUCT APPROVAL. | | FBC 107.2.1 |
|