Plan Review Notes
Plan Review Notes For Permit 20050786
Permit Number 20050786
Review Stop B
Sequence Number 1
Notes
Date Text
2020-05-28 10:09:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) INDICATE THE SYSTEM NUMBER AND THE MAXIMUM DESIGN
 PRESSURE FROM THE TABLES IN THE MODIFIED BITUMEN
 ROOFING PRODUCT APPROVAL. IF THE MAXIMUM DESIGN
 PRESSURE IS LESS THAN REQUIRED FOR THE PERIMETER AND
 CORNER AREAS IN EXPOSURE C IN A 170 MPH WINDSPEED
 (-95.7PSF FOR 15' MRH), THEN YOU WILL HAVE TO SUBMIT
 SIGNED AND SEALED ENHANCED FASTENING CALCULATIONS. FBC
 107.2.1
  
 2) INDICATE THE MINIMUM ATTACHMENT RESISTANCE FOR THE
 ROOF TILE BY MARKING THE APPLICABLE ITEMS IN TABLE 5 OR
 6 OF THE PRODUCT APPROVAL. FBC 107.2.1
  
 3) MARK THE APPLICABLE TILE PROFILE AND ADHESIVE
 PLACEMENT DETAIL ON THE TILE ADHESIVE PRODUCT APPROVAL.
 FBC 107.2.1