Plan Review Notes
Plan Review Notes For Permit 20050783
Permit Number 20050783
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2021-03-09 10:01:36THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE RESPONSE FROM THE FIRE SPRINKLER CONTRACTOR
 STATING A CODE SECTION FROM NFPA 13 MAY NOT
 SPECIFICALLY APPLY IN THIS INSTANCE.
  
 THE CODE SECTION QUOTED 8.15.3.2.3.1 FALLS UNDER
 8.15.3.2 NONCOMBUSTIBLULE CONSTRUCTION.
  
 THE PROPOSED STAIRS ARE WOOD/COMBUSTIBULE.
  
 A MORE SPECIFIC CODE INDICATES THAT FIRE SPRINKLESR
 SHALL BE INSTALLED UNDER COMBUSTIBLE STAIRS.
  
 PER NFPA 13
  
 8.15.3 STAIRWAYS.
  
 8.15.3.1 COMBUSTIBLE CONSTRUCTION. SPRINKLERS SHALL BE
 INSTALLED
 BENEATH ALL STAIRWAYS OF COMBUSTIBLE CONSTRUCTION.
 8.15.3.1.1 SPRINKLERS SHALL BE INSTALLED AT THE TOP OF
 COMBUSTIBLE
 STAIR SHAFTS.
 8.15.3.1.2* SPRINKLERS SHALL BE INSTALLED UNDER THE
 LANDINGS AT
 EACH FLOOR LEVEL.
 8.15.3.1.3 SPRINKLERS SHALL BE INSTALLED BENEATH THE
 LOWEST INTERMEDIATE
 LANDING.
  
  
 IN AN EFFORT TO MOVE THIS PROJECT FORWARD, THIS PERMIT
 WILL BE PASSED WITH PROVISO TO ADDRESS THE STIAIR FIRE
 PROTECTION OF THE SHOP DRAWINGS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  