2020-11-23 17:26:4011/23/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 2. PLEASE PROVIDE SPECIFICATIONS FOR TANKLESS ELECTRIC
 WATER HEATER PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. THERE TWO TUBS AND ONE SHOWER THAT SHOW AIR
 ADMITANCE VALVES BEHIND THEM, THEY NEED TO HAVE AN
 ACCESS PANEL OR YOU CAN RE-VENT THEM PLEASE SHOW ON
 ISOMETRIC OR MAKE NOTES ON PLANS FOR ACCESSIBLE
 LOCATION PER THE 2017 FBC SEC. 918.5 ACCESS AND
 VENTILATION.
  
 4. ON ISOMETRIC P-4 AND P-2, UNIT 4 HAS THE KITCHEN IN
 A BATHROOM GROUP WET VENT AND IT MUST RUN DOWNSTREAM OF
 THE GROUP PER THE 2017 FBC SEC. 912.1 HORIZONTAL WET
 VENTS PERMITTED.
  
 5. ON ISOMETRIC P-4 RISER D 2?, UNIT 2 BATH AND
 KITCHEN, AND RISER 3? HAVE ENTRY TO THE BUILDING WITH
 THE CLEANOUT AND MUST BE VENTED THROUGH ROOF AND MUST
 HAVE A MINIMUM OF ONE STACK VENT OR VENT STACK EXTENDED
 TO THE OUTDOORS TO THE OPEN AIR PER THE FBC SEC. P
 918.7. SHOW COMPLIANCE WITH THE PLANS.
  
 6. ON ISOMETRIC P-4 CLEANOUT NOT SHOWN ON BATH AND
 KITCHEN WITHIN 10 FT OF ENTERING BUILDING PER THE PER
 THE 2017 FBC 708.1.3 BUILDING DRAIN AND BUILDING SEWER
 JUNCTION.
  
 7. SHEET P-1 UNIT 1 HAS A STACKABLE WASHER AND DRYER
 AND ACCESS TO SHUT OFF VALVE MUST BE REACHABLE WITHOUT
 MOVING THE UNIT PLEASE MAKE NOT ON PLANS PER THE 2017
 FBC SEC. P 606.3. ACCESSIBLE SIGNIFIES ACCESS THAT
 REQUIRES THE REMOVAL OF AN ACCESS PANEL OR SIMILAR
 REMOVABLE OBSTRUCTION.
  
 8. SHEET P-1 UNIT 1 AND OTHERS DO NOT HAVE A WASHING
 MACHINE HOOK ARE THEY IN A DIFFERENT LOCATION, PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  