2020-11-23 17:26:40 | 11/23/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SIGNED AND SEALED DRAWINGS NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE |
| ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW |
| REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND |
| ASKING FOR THE FORM. |
| |
| 2. PLEASE PROVIDE SPECIFICATIONS FOR TANKLESS ELECTRIC |
| WATER HEATER PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. THERE TWO TUBS AND ONE SHOWER THAT SHOW AIR |
| ADMITANCE VALVES BEHIND THEM, THEY NEED TO HAVE AN |
| ACCESS PANEL OR YOU CAN RE-VENT THEM PLEASE SHOW ON |
| ISOMETRIC OR MAKE NOTES ON PLANS FOR ACCESSIBLE |
| LOCATION PER THE 2017 FBC SEC. 918.5 ACCESS AND |
| VENTILATION. |
| |
| 4. ON ISOMETRIC P-4 AND P-2, UNIT 4 HAS THE KITCHEN IN |
| A BATHROOM GROUP WET VENT AND IT MUST RUN DOWNSTREAM OF |
| THE GROUP PER THE 2017 FBC SEC. 912.1 HORIZONTAL WET |
| VENTS PERMITTED. |
| |
| 5. ON ISOMETRIC P-4 RISER D 2?, UNIT 2 BATH AND |
| KITCHEN, AND RISER 3? HAVE ENTRY TO THE BUILDING WITH |
| THE CLEANOUT AND MUST BE VENTED THROUGH ROOF AND MUST |
| HAVE A MINIMUM OF ONE STACK VENT OR VENT STACK EXTENDED |
| TO THE OUTDOORS TO THE OPEN AIR PER THE FBC SEC. P |
| 918.7. SHOW COMPLIANCE WITH THE PLANS. |
| |
| 6. ON ISOMETRIC P-4 CLEANOUT NOT SHOWN ON BATH AND |
| KITCHEN WITHIN 10 FT OF ENTERING BUILDING PER THE PER |
| THE 2017 FBC 708.1.3 BUILDING DRAIN AND BUILDING SEWER |
| JUNCTION. |
| |
| 7. SHEET P-1 UNIT 1 HAS A STACKABLE WASHER AND DRYER |
| AND ACCESS TO SHUT OFF VALVE MUST BE REACHABLE WITHOUT |
| MOVING THE UNIT PLEASE MAKE NOT ON PLANS PER THE 2017 |
| FBC SEC. P 606.3. ACCESSIBLE SIGNIFIES ACCESS THAT |
| REQUIRES THE REMOVAL OF AN ACCESS PANEL OR SIMILAR |
| REMOVABLE OBSTRUCTION. |
| |
| 8. SHEET P-1 UNIT 1 AND OTHERS DO NOT HAVE A WASHING |
| MACHINE HOOK ARE THEY IN A DIFFERENT LOCATION, PLEASE |
| CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |