2020-12-14 16:01:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) PLEASE PROVIDE A COMPLETE SCOPE OF WORK FOR THIS |
| PROJECT. |
| |
| IT APPEARS THAT THE ENTIRE BUILDING IS BEING REMODELED |
| WHICH WOULD BE REQUIRED TO BE CONSTRUCTED A A NEW |
| OCCUPANCY. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| 2) THERE IS NO INDICATION OF COMPLAINCE WITH ANY FIRE |
| CODES. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101. |
| |
| THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES: |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2013 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2013 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2013 EDITION. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2013 EDITION. |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND |
| COMPLIANCE. |
| |
| |
| |
| 3) PLEASE PROVIDE THE NEW OCCUPANCY TYPE AS IT APPEARS |
| TO BE AN APARTMENT OCCUPANCY AND COMPLY WITH THE |
| REQUIRMENTS OF NFPA 30. |
| |
| CHAPTER 30 NEW APARTMENT BUILDINGS |
| 30.1 GENERAL REQUIREMENTS. |
| 30.1.1 APPLICATION. |
| 30.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY |
| TO NEW |
| BUILDINGS OR PORTIONS THEREOF USED AS APARTMENT |
| OCCUPANCIES. (SEE |
| 1.3.1.) |
| |
| PLEASE PROVIDE DETAILS |
| |
| |
| |
| 4) THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM |
| |
| 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| AN APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| ACCORDANCE WITH |
| 30.3.5.2. |
| 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| INSTALLED, EITHER FOR |
| TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE |
| INSTALLED IN |
| ACCORDANCE WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 |
| AND 30.3.5.4. IN |
| BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE, |
| SYSTEMS IN |
| ACCORDANCE WITH NFPA 13R, STANDARD FOR THE INSTALLATION |
| OF |
| SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES, |
| SHALL BE |
| PERMITTED. |
| |
| REQUIRED F.A.C. 61G ARE REQUIRED TO BE SUBMITTED WITH |
| THIS MASTER PERMIT. |
| |
| PLEASE PROVIDE. |
| |
| |
| 5) THERE ARE NO INDICATIONS OF A FIRE ALARM SYSTEM. |
| |
| A FIRE SPRINKLER ALARM IS REQUIRED AND SHALL BE |
| MONITORED. |
| |
| 9.7.2 SUPERVISION. |
| 9.7.2.1* SUPERVISORY SIGNALS. |
| 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS |
| ARE REQUIRED BY |
| ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS |
| SHALL BE INSTALLED |
| AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72, |
| NATIONAL FIRE |
| ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY |
| SIGNAL SHALL BE |
| PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE |
| SATISFACTORY |
| OPERATION OF THE SPRINKLER SYSTEM. |
| 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE |
| DISPLAYED EITHER AT |
| A LOCATION WITHIN THE PROTECTED BUILDING THAT IS |
| CONSTANTLY ATTENDED BY |
| QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED |
| RECEIVING |
| FACILITY. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDEGMENT |
| |
| |
| 6) THERE APPEARS TO BE A SIGNLE EXIT FROM THE 3RD FL |
| UNIT. |
| |
| 2 ARE REQUIRED. |
| |
| 30.2.4 NUMBER OF MEANS OF EGRESS. |
| 30.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL COMPLY |
| WITH |
| SECTION 7.4. |
| 30.2.4.2 THE MINIMUM NUMBER OF EXITS SHALL COMPLY WITH |
| 30.2.4.3, 30.2.4.4, OR 30.2.4.6. |
| 30.2.4.3 EVERY DWELLING UNIT SHALL HAVE ACCESS TO AT |
| LEAST TWO |
| SEPARATE EXITS REMOTELY LOCATED FROM EACH OTHER AS |
| REQUIRED BY |
| 7.5.1. |
| 30.2.4.4 DWELLING UNITS SHALL BE PERMITTED TO HAVE |
| ACCESS TO A |
| SINGLE EXIT, PROVIDED THAT ONE OF THE FOLLOWING |
| CONDITIONS IS MET: |
| (1) THE DWELLING UNIT HAS AN EXIT DOOR OPENING DIRECTLY |
| TO THE |
| STREET OR YARD AT THE FINISHED GROUND LEVEL. |
| (2) THE DWELLING UNIT HAS DIRECT ACCESS TO AN OUTSIDE |
| STAIR THAT |
| COMPLIES WITH 7.2.2 AND SERVES A MAXIMUM OF TWO UNITS, |
| BOTH OF WHICH ARE LOCATED ON THE SAME STORY. |
| (3) THE DWELLING UNIT HAS DIRECT ACCESS TO AN INTERIOR |
| STAIR THAT |
| SERVES ONLY THAT UNIT AND IS SEPARATED FROM ALL OTHER |
| PORTIONS |
| OF THE BUILDING BY FIRE BARRIERS HAVING A MINIMUM |
| 1-HOUR FIRE |
| RESISTANCE RATING, WITH NO OPENING THEREIN. |
| |
| 30.2.4.6 A SINGLE EXIT SHALL BE PERMITTED IN BUILDINGS |
| WHERE THE |
| TOTAL NUMBER OF STORIES DOES NOT EXCEED FOUR, PROVIDED |
| THAT ALL OF |
| THE FOLLOWING CONDITIONS ARE MET: |
| (1) THERE ARE FOUR OR FEWER DWELLING UNITS PER STORY. |
| (2) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH |
| 30.3.5. |
| (3) THE EXIT STAIRWAY DOES NOT SERVE MORE THAN ONE-HALF |
| STORY |
| BELOW THE LEVEL OF EXIT DISCHARGE. |
| (4) THE TRAVEL DISTANCE FROM THE ENTRANCE DOOR OF ANY |
| DWELLING |
| UNIT TO AN EXIT DOES NOT EXCEED 35 FT (10.7 M). |
| (5) THE EXIT STAIRWAY IS COMPLETELY ENCLOSED OR |
| SEPARATED FROM |
| THE REST OF THE BUILDING BY BARRIERS HAVING A MINIMUM |
| 1-HOUR |
| FIRE RESISTANCE RATING. |
| (6) ALL OPENINGS BETWEEN THE EXIT STAIRWAY ENCLOSURE |
| AND THE |
| BUILDING ARE PROTECTED WITH SELF-CLOSING DOOR |
| ASSEMBLIES |
| HAVING A MINIMUM 1-HOUR FIRE PROTECTION RATING. |
| (7) ALL CORRIDORS SERVING AS ACCESS TO EXITS HAVE A |
| MINIMUM 1- |
| HOUR FIRE RESISTANCE RATING. |
| (8) HORIZONTAL AND VERTICAL SEPARATION HAVING A MINIMUM |
| ?-HOUR |
| FIRE RESISTANCE RATING IS PROVIDED BETWEEN DWELLING |
| UNITS. |
| |
| PLEASE CORRECT OR PROVIDE DETAILS IN COMPLIANCE. |
| |
| |
| 7) THERE ARE INDICATIONS OF STAIR EXIT PAST UNPROTECTD |
| WINDOWS. |
| |
| 30.2.2.3 STAIRS. |
| 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE |
| PERMITTED. |
| |
| 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS. |
| 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE |
| INTERIOR OF THE |
| BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE |
| RATING REQUIRED FOR |
| ENCLOSED STAIRS WITH FIXED OR SELF-CLOSING OPENING |
| PROTECTIVES, |
| EXCEPT AS FOLLOWS: |
| (1) OUTSIDE STAIRS SERVING AN EXTERIOR EXIT ACCESS |
| BALCONY THAT HAS |
| TWO REMOTE OUTSIDE STAIRWAYS OR RAMPS SHALL BE |
| PERMITTED TO BE |
| UNPROTECTED. |
| (2) OUTSIDE STAIRS SERVING TWO OR FEWER ADJACENT |
| STORIES, INCLUDING |
| THE STORY WHERE THE EXIT DISCHARGES, SHALL BE PERMITTED |
| TO BE |
| UNPROTECTED WHERE THERE IS A REMOTELY LOCATED SECOND |
| EXIT. |
| (3) IN EXISTING BUILDINGS, EXISTING OUTSIDE STAIRS |
| SERVING THREE OR |
| FEWER ADJACENT STORIES, INCLUDING THE STORY WHERE THE |
| EXIT |
| DISCHARGES, SHALL BE PERMITTED TO BE UNPROTECTED WHERE |
| THERE IS |
| A REMOTELY LOCATED SECOND EXIT. |
| (4) THE FIRE RESISTANCE RATING OF A SEPARATION |
| EXTENDING 10 FT (3050 |
| MM) FROM THE STAIRS SHALL NOT BE REQUIRED TO EXCEED 1 |
| HOUR |
| WHERE OPENINGS HAVE A MINIMUM ?-HOUR FIRE PROTECTION |
| RATING. |
| (5) OUTSIDE STAIRS IN EXISTING BUILDINGS PROTECTED |
| THROUGHOUT BY AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 9.7 SHALL BE PERMITTED TO BE |
| UNPROTECTED. |
| 7.2.2.6.3.2 WALL CONSTRUCTION REQUIRED BY 7.2.2.6.3.1 |
| SHALL EXTEND AS |
| FOLLOWS: |
| (1) VERTICALLY FROM THE FINISHED GROUND LEVEL TO A |
| POINT 10 FT (3050 |
| MM) ABOVE THE TOPMOST LANDING OF THE STAIRS OR TO THE |
| ROOFLINE, |
| WHICHEVER IS LOWER |
| (2) HORIZONTALLY FOR NOT LESS THAN 10 FT (3050 MM) |
| |
| PLEASE REVIEW AND CORRECT AS APPLICABLE. |
| |
| |
| 8) THERE ARE NO INDICATIONS OF STAIR DETAILS IN |
| COMPLIANCE WITH THE FIRE CODE. |
| |
| 30.2.2.3 STAIRS. |
| 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE |
| PERMITTED. |
| |
| 7.2.2.4 GUARDS AND HANDRAILS. |
| 7.2.2.4.1 HANDRAILS. |
| |
| 7.2.2.4.5* HANDRAIL DETAILS. |
| |
| 7.2.2.4.6 GUARD DETAILS |
| |
| PLEASE PROVIDE SPECIFIC DETAILS OF COMPLIANCE. |
| |
| |
| |
| 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |