Plan Review Notes
Plan Review Notes For Permit 20050783
Permit Number 20050783
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-12-14 16:01:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) PLEASE PROVIDE A COMPLETE SCOPE OF WORK FOR THIS
 PROJECT.
  
 IT APPEARS THAT THE ENTIRE BUILDING IS BEING REMODELED
 WHICH WOULD BE REQUIRED TO BE CONSTRUCTED A A NEW
 OCCUPANCY.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 2) THERE IS NO INDICATION OF COMPLAINCE WITH ANY FIRE
 CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES:
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND
 COMPLIANCE.
  
  
  
 3) PLEASE PROVIDE THE NEW OCCUPANCY TYPE AS IT APPEARS
 TO BE AN APARTMENT OCCUPANCY AND COMPLY WITH THE
 REQUIRMENTS OF NFPA 30.
  
 CHAPTER 30 NEW APARTMENT BUILDINGS
 30.1 GENERAL REQUIREMENTS.
 30.1.1 APPLICATION.
 30.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO NEW
 BUILDINGS OR PORTIONS THEREOF USED AS APARTMENT
 OCCUPANCIES. (SEE
 1.3.1.)
  
 PLEASE PROVIDE DETAILS
  
  
  
 4) THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH
 30.3.5.2.
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR
 TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE
 INSTALLED IN
 ACCORDANCE WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3
 AND 30.3.5.4. IN
 BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE,
 SYSTEMS IN
 ACCORDANCE WITH NFPA 13R, STANDARD FOR THE INSTALLATION
 OF
 SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES,
 SHALL BE
 PERMITTED.
  
 REQUIRED F.A.C. 61G ARE REQUIRED TO BE SUBMITTED WITH
 THIS MASTER PERMIT.
  
 PLEASE PROVIDE.
  
  
 5) THERE ARE NO INDICATIONS OF A FIRE ALARM SYSTEM.
  
 A FIRE SPRINKLER ALARM IS REQUIRED AND SHALL BE
 MONITORED.
  
 9.7.2 SUPERVISION.
 9.7.2.1* SUPERVISORY SIGNALS.
 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS
 ARE REQUIRED BY
 ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS
 SHALL BE INSTALLED
 AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72,
 NATIONAL FIRE
 ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY
 SIGNAL SHALL BE
 PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE
 SATISFACTORY
 OPERATION OF THE SPRINKLER SYSTEM.
 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE
 DISPLAYED EITHER AT
 A LOCATION WITHIN THE PROTECTED BUILDING THAT IS
 CONSTANTLY ATTENDED BY
 QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED
 RECEIVING
 FACILITY.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDEGMENT
  
  
 6) THERE APPEARS TO BE A SIGNLE EXIT FROM THE 3RD FL
 UNIT.
  
 2 ARE REQUIRED.
  
 30.2.4 NUMBER OF MEANS OF EGRESS.
 30.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL COMPLY
 WITH
 SECTION 7.4.
 30.2.4.2 THE MINIMUM NUMBER OF EXITS SHALL COMPLY WITH
 30.2.4.3, 30.2.4.4, OR 30.2.4.6.
 30.2.4.3 EVERY DWELLING UNIT SHALL HAVE ACCESS TO AT
 LEAST TWO
 SEPARATE EXITS REMOTELY LOCATED FROM EACH OTHER AS
 REQUIRED BY
 7.5.1.
 30.2.4.4 DWELLING UNITS SHALL BE PERMITTED TO HAVE
 ACCESS TO A
 SINGLE EXIT, PROVIDED THAT ONE OF THE FOLLOWING
 CONDITIONS IS MET:
 (1) THE DWELLING UNIT HAS AN EXIT DOOR OPENING DIRECTLY
 TO THE
 STREET OR YARD AT THE FINISHED GROUND LEVEL.
 (2) THE DWELLING UNIT HAS DIRECT ACCESS TO AN OUTSIDE
 STAIR THAT
 COMPLIES WITH 7.2.2 AND SERVES A MAXIMUM OF TWO UNITS,
 BOTH OF WHICH ARE LOCATED ON THE SAME STORY.
 (3) THE DWELLING UNIT HAS DIRECT ACCESS TO AN INTERIOR
 STAIR THAT
 SERVES ONLY THAT UNIT AND IS SEPARATED FROM ALL OTHER
 PORTIONS
 OF THE BUILDING BY FIRE BARRIERS HAVING A MINIMUM
 1-HOUR FIRE
 RESISTANCE RATING, WITH NO OPENING THEREIN.
  
 30.2.4.6 A SINGLE EXIT SHALL BE PERMITTED IN BUILDINGS
 WHERE THE
 TOTAL NUMBER OF STORIES DOES NOT EXCEED FOUR, PROVIDED
 THAT ALL OF
 THE FOLLOWING CONDITIONS ARE MET:
 (1) THERE ARE FOUR OR FEWER DWELLING UNITS PER STORY.
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 30.3.5.
 (3) THE EXIT STAIRWAY DOES NOT SERVE MORE THAN ONE-HALF
 STORY
 BELOW THE LEVEL OF EXIT DISCHARGE.
 (4) THE TRAVEL DISTANCE FROM THE ENTRANCE DOOR OF ANY
 DWELLING
 UNIT TO AN EXIT DOES NOT EXCEED 35 FT (10.7 M).
 (5) THE EXIT STAIRWAY IS COMPLETELY ENCLOSED OR
 SEPARATED FROM
 THE REST OF THE BUILDING BY BARRIERS HAVING A MINIMUM
 1-HOUR
 FIRE RESISTANCE RATING.
 (6) ALL OPENINGS BETWEEN THE EXIT STAIRWAY ENCLOSURE
 AND THE
 BUILDING ARE PROTECTED WITH SELF-CLOSING DOOR
 ASSEMBLIES
 HAVING A MINIMUM 1-HOUR FIRE PROTECTION RATING.
 (7) ALL CORRIDORS SERVING AS ACCESS TO EXITS HAVE A
 MINIMUM 1-
 HOUR FIRE RESISTANCE RATING.
 (8) HORIZONTAL AND VERTICAL SEPARATION HAVING A MINIMUM
 ?-HOUR
 FIRE RESISTANCE RATING IS PROVIDED BETWEEN DWELLING
 UNITS.
  
 PLEASE CORRECT OR PROVIDE DETAILS IN COMPLIANCE.
  
  
 7) THERE ARE INDICATIONS OF STAIR EXIT PAST UNPROTECTD
 WINDOWS.
  
 30.2.2.3 STAIRS.
 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS.
 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE
 BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE
 RATING REQUIRED FOR
 ENCLOSED STAIRS WITH FIXED OR SELF-CLOSING OPENING
 PROTECTIVES,
 EXCEPT AS FOLLOWS:
 (1) OUTSIDE STAIRS SERVING AN EXTERIOR EXIT ACCESS
 BALCONY THAT HAS
 TWO REMOTE OUTSIDE STAIRWAYS OR RAMPS SHALL BE
 PERMITTED TO BE
 UNPROTECTED.
 (2) OUTSIDE STAIRS SERVING TWO OR FEWER ADJACENT
 STORIES, INCLUDING
 THE STORY WHERE THE EXIT DISCHARGES, SHALL BE PERMITTED
 TO BE
 UNPROTECTED WHERE THERE IS A REMOTELY LOCATED SECOND
 EXIT.
 (3) IN EXISTING BUILDINGS, EXISTING OUTSIDE STAIRS
 SERVING THREE OR
 FEWER ADJACENT STORIES, INCLUDING THE STORY WHERE THE
 EXIT
 DISCHARGES, SHALL BE PERMITTED TO BE UNPROTECTED WHERE
 THERE IS
 A REMOTELY LOCATED SECOND EXIT.
 (4) THE FIRE RESISTANCE RATING OF A SEPARATION
 EXTENDING 10 FT (3050
 MM) FROM THE STAIRS SHALL NOT BE REQUIRED TO EXCEED 1
 HOUR
 WHERE OPENINGS HAVE A MINIMUM ?-HOUR FIRE PROTECTION
 RATING.
 (5) OUTSIDE STAIRS IN EXISTING BUILDINGS PROTECTED
 THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7 SHALL BE PERMITTED TO BE
 UNPROTECTED.
 7.2.2.6.3.2 WALL CONSTRUCTION REQUIRED BY 7.2.2.6.3.1
 SHALL EXTEND AS
 FOLLOWS:
 (1) VERTICALLY FROM THE FINISHED GROUND LEVEL TO A
 POINT 10 FT (3050
 MM) ABOVE THE TOPMOST LANDING OF THE STAIRS OR TO THE
 ROOFLINE,
 WHICHEVER IS LOWER
 (2) HORIZONTALLY FOR NOT LESS THAN 10 FT (3050 MM)
  
 PLEASE REVIEW AND CORRECT AS APPLICABLE.
  
  
 8) THERE ARE NO INDICATIONS OF STAIR DETAILS IN
 COMPLIANCE WITH THE FIRE CODE.
  
 30.2.2.3 STAIRS.
 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
  
 7.2.2.4.5* HANDRAIL DETAILS.
  
 7.2.2.4.6 GUARD DETAILS
  
 PLEASE PROVIDE SPECIFIC DETAILS OF COMPLIANCE.
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  