Plan Review Notes For Permit 20050783 |
Permit Number |
20050783 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-03 14:31:05 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE APPLICATION INDICATES THAT THE SCOPE OF WORK FOR | | THIS PERMIT IS TO REPAIR AND REPLACE ROTTEN WOOD | | RELATED TO A REROOF PERMIT. PRODUCT APPROVALS FOR ROOF | | COVERING MATERIALS WERE UPLOADED. THEY SHOULD BE WITH | | THE REROOFING PERMIT DOCUMENTS NOT THIS ONE. FBC | | 107.2.1 | | | | 2) SUBMIT A DETAILED SCOPE OF WORK FOR THIS PROJECT. | | FBC 107.2.1 | | | | 3) SUBMIT PLANS SHOWING THE AREAS OF THE ROOF WHERE THE | | REPAIRS ARE NEED. THE ADDRESS OF THE PROPERTY AND THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE IS | | REQUIRED TO BE ON THE PLAN. FBC 107.2.1 | | | | 4) SIGNED AND SEALED TRUSS REPAIR DETAILS FROM AN | | ENGINEER WILL BE RQUIRED IF TRUSSES ARE REPAIRED. FBC | | 107 |
|