2020-05-29 15:57:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS IS A MULTI-STORY MULTI-UNIT CONDO BUILDING
 WHICH IS GOVERNED BY THE FBC BUILDING RATHER THAN THE
 FBC RESIDENTIAL. IT IS LOCATED IN EXPOSURE D WITH A 170
 MPH VULT WINDSPEED. PART OF THE BUILDING APPEARS TO BE
 THREE HABITABLE FLOORS LOCATED ABOVE A PARKING GARAGE,
 WHICH MEANS TO THE ROOF HEIGHT IS 40 FEET OR MORE.
 SUBMIT SIGNED AND SEALED WINDLOAD CALCULATIONS FOR THE
 OPENINGS FROM A FLORIDA LICENSED ENGINEER. FBC 107
 NOTE: ORIGNAL SIGNATURES ARE REQUIRED ON PAPER
 SUBMITTALS AND DIGITAL SIGNATURES ARE REQUIRED ON
 ELECTRONICALLY SUBMITTED PLANS.