2020-08-28 08:04:52PLAN REVIEW GENERATOR ? FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CITY RECORDS INDICATE AN EXISTING GAS SERVICE AT THIS
 RESIDENCE.
  
 1) GAS ISOMETRIC DRAWING:
 1A) PROVIDE AN ISO DRAWING SHOWING THE ENTIRE SYSTEM
 INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST
 REMOTE OUTLET. THE BTUH LOAD OF EACH EXISTING APPLIANCE
 AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON
 THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES.
 NOTE: YOU MAY PROVIDE THE EXISTING LOAD AS ONE
 CALCULATION ON THE GAS RISER
  
  