Plan Review Notes
Plan Review Notes For Permit 20050732
Permit Number 20050732
Review Stop P
Sequence Number 2
Notes
Date Text
2020-07-20 16:09:432ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20050732
 7/20/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS REMAINING FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITONAL NOTES IN CAPITAL LETTERS.
  
 1) SHEET 1.1: PROVIDE A PLUMBING FIXTURE CALCULATION
 SCHEDULE ON THE PLAN- TABLE 403.3 FBC P. SHOW THE
 REQUIRED AND PROVIDED FIXTURES IN THE SCHEDULE. PLEASE
 NOTE A DRINKING FOUNTAIN IS REQUIRED FOR A2
 OCCUPANCIES. REFER TO SECTION 410 FBC P, AND SECTIONS
 211 AND 602 FBC ACC FOR FURTHER INFORMATION AND CODE
 COMPLIANCE REQUIREMENTS. THE PLUMBING FIXTURE
 CALCULATION DOES NOT INDICATE THE REQUIRED DRINKING
 FOUNTAIN. REFER TO SECTION 410.4: THE KAVA BAR IS NOT A
 RESTAURANT THEREFORE SUBSTITUTION OF WATER PROVIDED TO
 CUSTOMERS IN CONTAINERS FREE OF CHARGE DOES NOT MEET
 COMPLIANCE.
  
 REFER TO SECTION 211.1.2 FBC ACC, AND TABLE 404.3 FBC
 P. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 SECTIONS 602.1 ? 602.6, AND ONE SHALL COMPLY WITH
 602.7. SECTION 602.7 REQUIRES THAT SPOUT OUTLETS FOR
 STANDING PERSONS SHALL BE 38 INCHES MINIMUM AND 43
 INCHES MAXIMUM FROM THE FINISHED FLOOR. REVISE THE
 PLANS TO SHOW COMPLIANCE AND PROVIDE THESE DETAILS:
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
  
 2) SHEET 1.1: CORRECT THE NOTE AT THE TOILET ROOM
 INDICATING 30"X48" CLEAR FLOOR SPACE AT THE WATER
 CLOSET. CLEARANCE AROUND WATER CLOSETS SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL- SECTION 604.3.1 FBC ACC. TO AVOID
 CONFUSION IN THE FIELD PLEASE INDICATE THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET- 60? W X 56? D.
  
 3) SHEET 1.1: THE MOUNTING LOCATIONS AND HEIGHTS SHOWN
 IN THE TOILET ACCESSORY SCHEDULE ARE NOT IN COMPLIANCE
 WITH THE FBC ACC. IN ORDER TO EXPEDITE THE REVIEW
 PLEASE PROVIDE ENLARGED DIMENSIONED DETAILS AND
 ELEVATION VIEWS INDICATING: SEE NOTES BELOW FOR NEW
 SHEET 4.1
 E) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3 THE HEIGHT OF THE FRONT
 RIM OF THE LAVBATORY SHALL BE 34? FROM THE FINISHED
 FLOOR.
 F) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 306. NOT PROVIDED.
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5. GRAB BAR HEIGHT IS SHOWN TO THE
 CENTERLINES OF THE GRAB BARS AND NOT TO THE TOP OF THE
 GRIPPING SURFACES.
 H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6. NOT PROVIDED.
 I) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 PAPER DISPENSERS- SECTION 604.7 THE TOILET PAPER
 DISPENSER SHALL BE INSTALLED 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
 J) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 8) 4.1: PROVIDE A PLUMBING DEVICE SCHEDULE INDICATING
 MAKES AND MODELS, AND LISTING AND LABELING FOR THE
 MIXING VALVE, REQUIRED WATER HAMMER ARRESTORS, AND
 BACKFLOW PREVENTERS- SECTIONS 604.9, 607.1.2, AND 608.3
 FBC P. SHOW ALL DEVICE LOCATIONS ON THE WATER RISER.
 THE WATTS SD-2 BACKFLOW PREVENTER IS DESIGNED FOR USE
 ON CARBONATED BEVERAGE DISPENSERS. PLEASE REVIEW THE
 SPECS FOR THE DEVICE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  