2020-07-01 13:37:57PERMIT #20050732
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1.SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 2.FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE.
 3. INDICATE THE BREAKDOWN OF THE OCCUPANT LOAD OF THE
 OCCUPPIED FLOOR AREA
 IE. BAR AREA
 IE. CUSTOMER AREA
  
 BRITTANY WOODS
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4754
  