2020-06-10 08:28:052017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050732
 ADD: 1540 PALM BEACH LAKES BLVD. # 130
 CONT: PHILIP E. JOHNSON INC.
 TEL: 561-366-1034
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 10TH/ 2020
 ACTION: DENIED
  
 1) SHEET 1.1:
  
 1A) SHEET 1.1 UNDER THE HEADING OF PROJECT DATA LIST
 THE FLOOR AREA OF 1,716 SQ. FT. BUT THE OCCUPANT LOAD
 OF 46 IS TAKEN ON 609 SQ. FT. PLEASE PROVIDE THE
 OCCUPANT LOAD FOR THE WHOLE FLOOR AREA. THE FLOOR AREA
 SHOULD BE TAKEN ON A NET SQUARE FOOTAGE. 2017 FBC-B
 TABLE 1004.1.2 AND DEFINITION OF NET FLOOR AREA. 2017
 FBC-B 201: FLOOR AREA, NET. THE ACTUAL OCCUPIED AREA
 NOT INCLUDING UNOCCUPIED ACCESSORY AREAS SUCH AS
 CORRIDORS, STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS
 AND CLOSETS.
  
 1B) THE FLOOR PLAN HAS NOTES ON THE PLAN THAT THE PLAN
 WAS DESIGNED UNDER BOTH THE PRESCRIPTIVE METHOD AND
 LEVEL II WORK AREA METHOD OF COMPLIANCE. PLEASE REVIEW
 IN THE 2017 EXISTING BUILDING CODE SECTION 301.1 THE
 REPAIRS, ALTERATIONS, CHANGE OF OCCUPANCY, ADDITIONS,
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 301.1
 THROUGH 301.1.3 AS SELECTED BY THE DESIGNER OF RECORD.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER. PLEASE CHOOSE ONE
 METHOD OF DESIGN.
  
 1C) PLEASE ALSO NOTE WITH THE REAR PORTION OF THE FLOOR
 NOT BEING A POURED CONCRETE FLOOR JUST LEFT DIRT IT
 WOULD APPEAR THIS UNIT WAS LEFT TO BE CONSIDERED A
 VANILLA SHELL, NO OCCUPANCY TYPE. WITH THE NEW PROPOSED
 OCCUPANCY A CHANGE OF OCCUPANCY A WELL. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1D) THERE IS ALSO A NOTE ON THE PLAN, ADA COMPLIANCE OF
 A226/ A902 REQUIRING HANDICAPPED SEATING W/ CLEARANCES
 PER A306. SEE PLAN FOR DEDICATED TABLES. THIS PLAN DOES
 NOT SHOW ACCESSIBLE SEATING AT ALL. 2017 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 THIS SHEET DOES NOT SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE;
 1E)) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 1F) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 1G) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 1H) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTER (HIGH TOPS), AND BOOTHS. EXAMPLES
 OF WORK SURFACES INCLUDE WRITING SURFACES, STUDY
 CARRELS, STUDENT LABORATORY STATIONS, BABY CHANGING AND
 OTHER TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 1H)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1H)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1I) SHEET 1.1 UNDER THE HEADING TOILET ACCESSORY
 SCHEDULE SHOWS:
  
 1I)(1) GB & GB-1 BOTH TAKING THE VERTICAL MEASUREMENT
 FROM CENTERLINE OF THE GRAB BAR TO FINISH FLOOR. 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 1I)(2) THE MEASUREMENT FOR THE PLACEMENT OF THE TOILET
 PAPER TAKEN FROM THE BACK WALL 36 INCHES FROM THE REAR
 CORNER. . 2017 ACCESSIBILITY CODE SECTION 604.7. TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE
 7-9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTER LINE OF THE DISPENSER. THE
 OUTLET OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND
 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT
 BE LOCATED BEHIND THE GRAB BARS.
  
 1J) UNDER THE HEADING PROJECT DATA THE PLAN DOES NOT
 INCLUDE IN THE 2017 FBC-B 2902.1 MINIMUM NUMBER OF
 FIXTURES NOR 2902.1.1 FIXTURE CALCULATIONS, AND TABLE
 2902.1.
  
 1K) THE PLAN IS SILENT AS TO THE REQUIRED EXIT
 HARDWARE, PLEASE REVIEW IN THE 2017 FBC-B SECTION
 1010.1.10 PANIC HARDWARE WHEN THERE IS AN OCCUPANT LOAD
 OF 50 OR MORE IN GROUP A OCCUPANCIES.
  
 1L) PLEASE ALSO UPDATE THE PLAN NOW 2 MEANS OF EGRESS
 ARE REQUIRED WITH AN OCCUPANT LOAD OF 50 OR MORE. SEE
 TABLE 1006.2.1.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved