Plan Review Notes For Permit 20050714 |
Permit Number |
20050714 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-05-29 15:17:04 | SHUTTER | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) BUILDING HEIGHT SHOWN ON THE ATTACHMENT SCHEDULE MAY | | BE INCORRECT. WIND DESIGNS ARE BASED ON THE BUILDING | | HEIGHT NOT WHERE THE UNIT IS. BUILDING APPEARS TO BE | | OVER 30 FEET HIGH. | | 2) PLEASE PROVIDE DIGITALLY SIGNED AND SEALED WIND | | DESIGN PRESSURES FROM AN ARCHITECT OR ENGINEER.(SHOWING | | THE WIND DESIGN CRITERIA) FBC 1609 |
|