2020-05-27 11:03:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATIONS OF A HEAT MAP SHOWINGS AREAS
 OF COVERAGE USED TO SUPPORT THE DESIGN/PLACEMENT OF THE
 ANTENNAS.
  
 PLEASE PROVIDE A PRE/POST HEAT MAP.
  
  
  
 2) PLEASE PROVIDE DETAILS OF HOW AND WHERE CABLES WILL
 BE RUN WITHIN THE CORRIDORS AND PARKING GARAGE AREAS
 THAT MEET SURVIVALBILITY.
  
  
  
 3) PLEASE PROVIDE DETAILS OF THE LISTING FOR THE
 PENETRATIONS OF APPLICABLE FIRE RATING WALLS/FLOORS OF
 ALL CABLES/EQUIPMENT.
  
  
  
 4) YOU SHALL MAKE CONTACT AND COORDINATE WITH MARK
 FILLA, PALM BEACH COUNTY, PUBLIC SAFETY RADIO SYSTEMS
 MANAGER, FOR ALL RADIO SIGNAL DETAILS, OUTBOUND SIGNAL
 STRENGTH AND ANTENNA DIRECTION, AS OUR RADIOS OPERATE
 ON THAT SYSTEM.
  
 [email protected] 561-233-0837
  
 PLEASE PORVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  