Date |
Text |
2020-06-01 09:38:23 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20050707 |
| ADD: 501 S FLAGLER DR. 12TH FL. COMMON RESTROOMS |
| CONT: ANDERSON MOORE CONSTRUCTION |
| TEL: 561-348-4805 |
| E-MAIL: PERMITSAANDJ PERMITS.COM |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JUNE 01/2020 |
| ACTION: DENIED |
| |
| 1) THE LIFE SAFETY SHEET LS-ALS1.1, CODE ANALYSIS , |
| MEANS OF EGRESS FOR COMMON AREAS STATES AN OCCUPANT |
| LOAD IS 99 PERSONS (ENTIRE FLOOR) 1 EXIT REQUIRED, 2 |
| PROVIDED. |
| PLEASE REVIEW IN THE 2017 FBC-B TABLE 1006.3.2(2) ONLY |
| B, F,M,& S ARE ALLOWED TO HAVE 1 EXIT ABOVE THE GRADE |
| PLANE. ALL OCCUPANCIES 3RD FLOOR AND ABOVE ARE REQUIRED |
| 2 MEANS OF EGRESS TO GRADE. PLEASE CORRECT THE PLAN. |
| |
| 2) THIS FLOOR PLAN DOES NOT SHOW THE RESTROOMS BEING |
| ACCESSIBLE NOR IS THERE ANY STATEMENT SHOWING |
| COMPLIANCE WITH THE 2017 FBC-B SECTIONS: |
| 2902.3.2. LOCATION OF TOILET FACILITIES (ACCESSIBLE) IN |
| OCCUPANCIES OTHER THAN MALLS . |
| 2902.4.1 DIRECTIONAL SIGNAGE. |
| 2017 ACCESS. CODE SECTIONS: |
| |
| SIGNAGE 703. 703.1 SIGNS SHALL COMPLY WITH 703. WHERE |
| BOTH VISUAL AND TACTILE CHARACTERS ARE REQUIRED, EITHER |
| ONE SIGN WITH BOTH VISUAL AND TACTILE CHARACTERS, OR |
| TWO SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH |
| TACTILE CHARACTERS, SHALL BE PROVIDED. |
| |
| SIGNAGE TACTILE CHARACTERS ABOVE FINISH FLOOR OR GROUND |
| 2014 ACCESSIBILITY CODE. 703.4.1 HEIGHT ABOVE FINISH |
| FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE |
| LOCATED 48 INCHES MINIMUM ABOVE THE FINISH FLOOR OR |
| GROUND SURFACE, MEASURED FROM THE BASELINE OF THE |
| LOWEST TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE |
| BASELINE OF THE HIGHEST TACTILE CHARACTER. |
| |
| SIGNAGE. 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND. |
| TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES |
| MINIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE, |
| MEASURED FROM THE BASELINE OF THE LOWEST TACTILE |
| CHARACTER AND 60 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| OR GROUND SURFACE, MEASURED FROM THE BASELINE OF THE |
| HIGHEST TACTILE CHARACTER. |
| |
| BRAILLE. 703.3. BRAILLE SHALL BE CONTRASTED (GRADE 2) |
| AND SHALL COMPLY WITH 703.3 AND 703.4. |
| |
| BRAILLE. 703.3.2 POSITION. BRAILLE SHALL BE POSITIONED |
| BELOW THE CORRESPONDING TEXT. IF THE TEXT IS |
| MULTI-LINED, THE BRAILLE SHALL BE BELOW THE ENTIRE |
| TEXT. BRAILLE SHALL BE SEPARATED 3/8 INCH MINIMUM FROM |
| ANY OTHER TACTILE CHARACTER AND 3/8 INCH MINIMUM FROM |
| RAISED BORDERS AND DECORATIVE ELEMENTS. |
| |
| 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE |
| TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |