Plan Review Notes
Plan Review Notes For Permit 20050707
Permit Number 20050707
Review Stop B
Sequence Number 1
Notes
Date Text
2020-06-01 09:38:232017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050707
 ADD: 501 S FLAGLER DR. 12TH FL. COMMON RESTROOMS
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: 561-348-4805
 E-MAIL: PERMITSAANDJ PERMITS.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 01/2020
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET LS-ALS1.1, CODE ANALYSIS ,
 MEANS OF EGRESS FOR COMMON AREAS STATES AN OCCUPANT
 LOAD IS 99 PERSONS (ENTIRE FLOOR) 1 EXIT REQUIRED, 2
 PROVIDED.
 PLEASE REVIEW IN THE 2017 FBC-B TABLE 1006.3.2(2) ONLY
 B, F,M,& S ARE ALLOWED TO HAVE 1 EXIT ABOVE THE GRADE
 PLANE. ALL OCCUPANCIES 3RD FLOOR AND ABOVE ARE REQUIRED
 2 MEANS OF EGRESS TO GRADE. PLEASE CORRECT THE PLAN.
  
 2) THIS FLOOR PLAN DOES NOT SHOW THE RESTROOMS BEING
 ACCESSIBLE NOR IS THERE ANY STATEMENT SHOWING
 COMPLIANCE WITH THE 2017 FBC-B SECTIONS:
 2902.3.2. LOCATION OF TOILET FACILITIES (ACCESSIBLE) IN
 OCCUPANCIES OTHER THAN MALLS .
 2902.4.1 DIRECTIONAL SIGNAGE.
 2017 ACCESS. CODE SECTIONS:
  
 SIGNAGE 703. 703.1 SIGNS SHALL COMPLY WITH 703. WHERE
 BOTH VISUAL AND TACTILE CHARACTERS ARE REQUIRED, EITHER
 ONE SIGN WITH BOTH VISUAL AND TACTILE CHARACTERS, OR
 TWO SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH
 TACTILE CHARACTERS, SHALL BE PROVIDED.
  
 SIGNAGE TACTILE CHARACTERS ABOVE FINISH FLOOR OR GROUND
 2014 ACCESSIBILITY CODE. 703.4.1 HEIGHT ABOVE FINISH
 FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE
 LOCATED 48 INCHES MINIMUM ABOVE THE FINISH FLOOR OR
 GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 LOWEST TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 SIGNAGE. 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 MINIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE LOWEST TACTILE
 CHARACTER AND 60 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 HIGHEST TACTILE CHARACTER.
  
 BRAILLE. 703.3. BRAILLE SHALL BE CONTRASTED (GRADE 2)
 AND SHALL COMPLY WITH 703.3 AND 703.4.
  
 BRAILLE. 703.3.2 POSITION. BRAILLE SHALL BE POSITIONED
 BELOW THE CORRESPONDING TEXT. IF THE TEXT IS
 MULTI-LINED, THE BRAILLE SHALL BE BELOW THE ENTIRE
 TEXT. BRAILLE SHALL BE SEPARATED 3/8 INCH MINIMUM FROM
 ANY OTHER TACTILE CHARACTER AND 3/8 INCH MINIMUM FROM
 RAISED BORDERS AND DECORATIVE ELEMENTS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  