Date |
Text |
2020-06-25 09:30:08 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20050706 505 S FLAGLER DR FL 11 |
| |
| PLUMBING COMMENTS: DENIED |
| PLAN SHEET PO.1 INDICATES A TANKLESS WATER HEATER ABOVE |
| THE CEILING TO PROVIDE HOT WATER TO LAVATORY. THE RISER |
| DIAGRAM SHOWS A VALVED DEDICATED HOT WATER LINE FROM |
| DISTRIBUTION TO SUPPLY THE LAVATORIES. PER WPB FBC |
| 107.2.1, CLARIFY. |
| |
| PROVISO: |
| RE: PLAN SHEET A2.1.1PER FBC ACC 609.4, GRAB BARS SHALL |
| BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES |
| MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT |
| CENTERLINE |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20050706 505 S FLAGLER DR FL 11 |
| |
| |