2020-06-03 08:19:16 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT -20050699 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) MASTER PERMIT 19110910 SHEET M-1 SPECS L2 AND L3 |
| LOUVERS IN THE GENERATOR ROOM TO BE 80X48. SHEET E10 |
| ?GENERATOR ROOM DETAIL? CALLS FOR THE EXHAUST LOUVER TO |
| BE 108X108. PLEASE CLARIFY THIS FOR BOTH PROJECTS. FBC |
| FS 107.2.1 |
| |
| 2) PLEASE PROVIDE CALCULATIONS FOR THE COMBUSTION AIR |
| NEEDED FOR THIS GENERATOR AND THE MINIMUM SIZE OUTDOOR |
| OPENING. FBC FG 304.6 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |