Plan Review Notes
Plan Review Notes For Permit 20050699
Permit Number 20050699
Review Stop M
Sequence Number 1
Notes
Date Text
2020-06-03 08:19:161ST REVIEW FBC-2017 MECHANICAL
 PERMIT -20050699
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MASTER PERMIT 19110910 SHEET M-1 SPECS L2 AND L3
 LOUVERS IN THE GENERATOR ROOM TO BE 80X48. SHEET E10
 ?GENERATOR ROOM DETAIL? CALLS FOR THE EXHAUST LOUVER TO
 BE 108X108. PLEASE CLARIFY THIS FOR BOTH PROJECTS. FBC
 FS 107.2.1
  
 2) PLEASE PROVIDE CALCULATIONS FOR THE COMBUSTION AIR
 NEEDED FOR THIS GENERATOR AND THE MINIMUM SIZE OUTDOOR
 OPENING. FBC FG 304.6
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  